Professional Documents
Culture Documents
Circuit Breakers
Circuit Breakers
Circuit Breakers
•This type of control is limited to low voltage and small capacity circuits where
frequent operations are not expected.
•The reason behind this is that fuses when blow out it takes some time to
replace and restore the supply to the customers.
•Secondly a fuse can’t interrupt heavy fault currents that results in the faults
on modern high voltage lines.
OPERATING MODES
•Under the fault condition the trip coils of the C.B. gets energized and
thus opens the CB.
HIGH
RESISTANCE
METHOD
REDUCTION IN
SPLITTING THE THE AREA OF
ARC CROSSECTION
OF THE ARC
ARC EXTINCTION BY HIGH RESISTANCE METHOD
•If the area of crossection of the arc is reduced the voltage necessary
to maintain the arc is increased .This can be obtained by letting the arc
pass through a narrower opening.
•The resistance of arc can be increased by splitting the arc into smaller
arcs in series.
ARC EXTINCTION BY HIGH RESISTANCE METHOD
LENGTHENING OF THE ARC
ARC INTENSITY
HIGH
MEDIUM IONIZED
GAS BLASTING
MEDIUM IONIZED
MEDIUM IONIZED
LOW
RESISTANCE
METHOD
HIGH
BLAST EFFECT
PRESSURE
ARC EXTINCTION BY LOW RESISTANCE METHOD
• The dielectric strength of the medium is proportional to the length of the gap
between contacts therefore by opening the contacts rapidly higher dielectric
strength can be achieved.
• If the pressure in the vicinity of the arc is increased. The density of the particles
constituting the discharge also increases. This causes high rate of deionization.
• Natural combination of ionized particles takes more rapidly if they are allowed to
cool thus deionization increases.
• If the ionized particles between the contacts are swept away and replaced by
deionized particles. Arc resistance will increase
ARC EXTINCTION BY LOW RESISTANCE METHOD
1. BY VOLTAGE CLASS
2. BY LOCATION
3. BY EXTERNAL DESIGN
4. BY ARC EXTINGUISHING MEDIUM
CLASSIFICATION ON THE BASIS OF VOLTAGE
• LIVE TANK
In live tank circuit breakers, the interrupter is located In an insulator
bushing, at a potential above ground potential. The live tank circuit
breakers are cheaper (with no current transformer), and require less
mounting space.
• DEAD TANK
In the dead tank circuit breakers, the switching device is located, with
suitable insulator supports, inside a metallic vessel at ground potential and
filled with insulating medium. In dead tank circuit breakers, the incoming
and outgoing conductors are taken out through suitable insulator
bushings, and low voltage type current transformers are located at lower
end of both insulator bushings, i.e at the line side and the load side.
CLASSIFICATION ON THE BASIS OF ARC
EXTINGUISHING MEDIUM
VACUUM CIRCUIT
BREAKER
TYPES OF
SF6 OIL CIRCUIT
CIRCUIT
CIRCUIT BREAKER BREAKER
BREAKER
AIR BLAST
CIRCUIT BREAKER
AIR CIRCUIT BREAKERS
• Air circuit breaker is defined as a circuit breaker, in which the contacts
open and close in air at atmospheric pressure. In general, the use of this
type of circuit breakers is restricted to low voltage applications or high
security installations where the risk of an oil fire or oil contamination of
the environment is too high to be tolerated. Countries following the
American practice used air circuit breakers almost exclusively for systems
up to 15 kV until the advent of the new vacuum and SF6 technologies.
VACCUM CIRCUIT BREAKER
• Advantages:
1.The vacuum circuit breakers are compact in size and have longer lives.
2.Operating energy requirements are low, because the mechanism must
move only relatively small masses at moderate speed, over very short
distances.
3.Because of the very low voltage across the metal vapor arc, energy is very
low.(Arc voltage is between 50 and 100V.)
4.Due to the very low arc energy, the rapid movement of the arc root over the
contact and to the fact that most of the metal vapor re-condenses on the
contact , contact erosion is extremely small.
5.There is no generation of gases during and after the circuit breaker
operation.
6.The outstanding feature of these breakers is that it can break any heavy
fault current perfectly just before the contacts reach a definite open
position.
VACCUM CIRCUIT BREAKER
• APPLICATIONS
For a country like Pakistan, where distances are quite long and
accessibility to remote areas are difficult, the installation of such outdoor,
maintenance-free circuit breakers should prove a definite advantage.
Vacuum circuit breakers are being employed for outdoor applications
ranging from 22 kv to 66 kv. This technology has been found to be most
suitable for medium voltage application though the experimental
interrupters for the 72.5 kv and 145 kv have been developed, they were
not found to be commercially viable
OIL CIRCUIT BREAKERS
• In such circuit breakers, some insulating oil (i.E., Transformer oil) is used as
an arc quenching medium. The contacts are opened under oil and an arc is
struck between them. The heat of the arc evaporates the surrounding oil
and dissociates it into a substantial volume of hydrogen gas at a high
pressure.
• 1.Oil absorbs the arc energy to produces hydrogen gas during arcing. The
hydrogen has excellent cooling properties and helps extinguish the arc.
• 2.The oil provides insulation for the live exposed contacts from the
earthed portions of the container.
• 2.The hydrogen generated during arcing, when combined with air, may
form an explosive mixture.
Positions
Rack In Position
Rack Out Position
Test Position
Types
Unit 1 &2
• Minimum Oil Circuit Breakers
• Vacuum Circuit Breakers
Unit 3 / 4 & 5 / 6
• Vacuum Circuit Breakers
Positions Of Breaker
BREAKER RACK IN
LOCAL MODE
• Electrically Turned Off
• Mechanically Turned ON & OFF
REMOTE MODE
• Electrically Turned ON / OFF from Control Room
Unit 3 / 4
• Air Circuit Breakers
Unit 5 / 6
• Air Circuit Breakers
BQPS 0.4 KV Switch Gear
POSITIONS
Rack In Position
Rack Out Position
Test Position
Positions Of Breaker
BREAKER RACK IN
LOCAL MODE
• Mechanically Turned ON by pressing Push Button.
• Mechanically Turned Off by pressing Push Button.
REMOTE MODE
• Electrically Turned ON / OFF from Control Room.
0.4 KV Switch Gear
Breaker Mechanism
Motorized Spring Charging
One Complete Operation
• Breaker Closed (Spring Charged)
• Breaker Opened (Spring Discharged)
After One Complete Operation Spring Charged Again by DC 220V Motor.
Ready For Next Operation.
• ARC VOLTAGE
IT IS THE VOLTAGE THAT APPEARS ACROSS THE CONTACTS OF CIRCUIT
BREAKER DURING THE ARCING PERIOD.
• RESTRIKING VOLTAGE
IT IS THE TRANSIENT VOLTAGE THAT APPEARS ACROSS THE CONTACTS AT
CURRENT ZERO OF AC CYCLE DURING ARCING PERIOD.
• RECOVERY VOLTAGE
• IT IS THE NORMAL VOLTAGE THAT APPEARS ACROSS THE CB AFTER FINAL
ARC EXTINCTION
Q&A
THANKS