Professional Documents
Culture Documents
Chapter - 4 Transmission Line Performance
Chapter - 4 Transmission Line Performance
VS VR ( R jX L ) I R (4.1b)
VR Z I R
Short transmission line ( cont’d…)
The phasor diagram of the line for lagging load power factor shown
in the above figure. From the right angled triangle ODC, we get
approximate expression,
short transmission line ( cont’d…)
An approximate expression for the sending end voltage VS can be
obtained as follows. Draw perpendicular from B and C on OA
produced as shown in Fig. a Then OC is nearly equal to OF i.e.,
OC = OF = OA + AF = OA + AG + GF
= OA + AG + BH
∴ VS = VR + I R cos φR + I XL sin φR
Solution 11,000
Receiving-end phase voltage = 6.360 VR
3
Line current = phase current ( assuming a star connection )
3,000 103
= 197 A
3 11 103 0.8
300 103
R
3 197 2
2.58 ohms
Example -1 cont’d
• Assuming that the conductors are manufactured from copper having a
resistance of 0.0137 ohms per meter for a cross-sectional area of 1 mm 2, the
conductor cross-section is 80 mm2 corresponding to a radius of 5 mm.
1 d
Inductance =L (1 4 log c ) 107 H / metre
2 r
X L L length
1 1.7 103
= 314 (1 4 log c ) 10 7 15 10 3
2 5
=5.75 ohms
VS VR I R R cos R I R X L sin R
= 6,350 + ( 197 2.58 0.8) + ( 197 5.75 0.6)
= 6,350 + 1057
= 7,407 V per phase
= 12,780 V line
( R cos R X L sin R ) VS VR
Regulation =I R =
VR VR
1,057
= 16.7 %
6,350
Problem-1
Nominal T method
In a nominal T method the total line capacitance is assumed to be concentrated at
the middle point of the line. The T representation of a line is shown in fig. below.
Z Y Z Y
Vs Vr (1 ) Ir ( Z )
2 4
Other quantities , such as phase shift, power input, efficiency, regulation, etc, can be
determined in the usual manner .
A=?
B=?
C=?
D=?
Medium transmission line cont’d
• Phasor diagram
Nominal π method.
• This method assumed that one-half of the total line capacitance is
concentrated at each end of the line and the total resistance and inductive
reactance are concentrated at the center.
Fig. (4.2c) shows the nominal π representation of the line.
Vs Vr I Z
Voltage at the sending-end
Y
Vr ( Ir Vr )Z
2
Z Y
(1 )Vr Z Ir
2 Y
Icd Vs
2
Sending-end current, Is I Icd
Z Y Y
[(1 )Vr Z Ir ]
2 2
Y ZY Y
Is Ir Vr [(1 )Vr Z Ir ]
2 2 2
Z Y2 ZY
( Y+ ) Vr ( 1 ) Ir
4 2
Medium transmission line cont’d
Phasor diagram
Vr Vr j 0
Let the load current be Ir. Since the load power factor is unity,
Ir I s 0 I s j 0
Sending-end voltage, Vs Vr I Z
=Vr j 0 ( Ir j14.96)( j 62.8)
=(Vr -939.5)+j 62.8 I r
10862
Ir 173 A
62.8
Problem-3
• A 3-phase, 50-Hz overhead transmission line 100 km long has the following
constants :
Resistance/km/phase = 0.1 Ω
Inductive reactance/km/phase = 0·2 Ω
Capacitive susceptance/km/phase = 0·04 × 10 −4 siemen
Determine (i) the sending end current (ii) sending end voltage (iii) sending
end power factor and (iv) transmission efficiency when supplying a balanced
load of 10,000 kW at 66 kV, p.f. 0·8 lagging. Use nominal T method.
• Solution. Figs. 10.13 (i) and 10.13 (ii) show the circuit diagram and phasor
diagram of the line respectively.
Problem-3 cont’d
Problem-3 cont’d
Long Transmission Line
Lines longer than 250 km (150 miles) are long transmission line
For long lines, it is not accurate enough to approximate the shunt
admittance by two constant capacitors at either end of the line.
Instead, both the shunt capacitance and the series impedance must be
treated as distributed quantities; the voltages and currents on the line
should be found by solving differential equations of the line.
However, it is possible to model a long transmission line as a π model
with a modified series impedance Z’ and a modified shunt admittance
Y’ and to perform calculations on that model using ABCD constants.
The modified values of series impedance and shunt admittance are:
Cont…
thus,