TROUBLESHOOTING

HEAT-PUMP

HEAT-RECOVERY

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING"


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :

– A MALFUNCTION WITHOUT ERROR INDICATION

– A MALFUNCTION BY SOME INDICATION.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 2


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION - INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
• REASON : GUARD TIMER

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 3


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
– EXAMPLE 2 : FAN DOES NOT START IN HEATING .
• REASON : COLD DRAFT PREVENTION 300 seconds.

T Indoor coil  T 
Indoor coil
2 2
35° 35°
C C

indoor fan indoor fan


start start
0 5 min 0 5 min
Tc
SENSPH 52°C

 indoor fan
start
0 5 min
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 4
m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
– EXAMPLE 2 : FAN DOES NOT START IN HEATING .
– EXAMPLE 3 : FAN STOPS AND SOME “GURGLING” SOUND .
• REASON : DEFROST OR OIL-RETURN STARTS.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 5


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
– EXAMPLE 2 : FAN DOES NOT START IN HEATING .
– EXAMPLE 3 : FAN STOPS AND SOME “GURGLING” SOUND .
– EXAMPLE 4 : SOMETIMES COOLING IS STOPPED.
• REASON : PREVENTIVE FREEZE-UP .
 Thermostat-OFF
 =expansion valve closed
 Fan forced L-speed
 Drain Pump ON

+7°C

-5°C

10 min 10 min time

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 6


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
– EXAMPLE 2 : FAN DOES NOT START IN HEATING .
– EXAMPLE 3 : FAN STOPS AND SOME “GURGLING” SOUND .
– EXAMPLE 4 : SOMETIMES COOLING IS STOPPED.
– EXAMLPE 5 : INDOOR UNIT CHANGES SWING FLAP .
• REASON : POSITION IS CHANGED TO AVOID CONDENSE ON
CASING AT AIR-OUTLET.

“Ceiling soiling prevention” Condense prevention


 60 Minutes
FXFQ&FXKQ
 20 Minutes
PØ FXHQ
P1 P0
 20 Minutes P3orP4
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 7
m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- INDOOR
• TYPICIAL EXAMPLES INDOOR :
– EXAMPLE 1 : COMPRESSOR DOES NOT START .
– EXAMPLE 2 : FAN DOES NOT START IN HEATING .
– EXAMPLE 3 : FAN STOPS AND SOME “GURGLING” SOUND .
– EXAMPLE 4 : SOMETIMES COOLING IS STOPPED.
– EXAMLPE 5 : INDOOR UNIT CHANGES SWING FLAP .
– EXAMPLE 6 : AIR FILTER CLEANING SYMBOL.
H
L
LL INDOOR FAN
OFF TIME

t1 + t2 + t3
ADD
FILTER COUNTER
HOLD
Σ TIME
(t..)
Σ (t..) > set
ON
FILTER SIGN
OFF
TIME
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 8
m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- Air curtain

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 9


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- OUTDOOR
• TYPICIAL EXAMPLES OUTDOOR :
– EXAMPLE 1 : NO HEATING :
• REASON : ABOVE 23°C OUTDOOR AMBIENT

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 10


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- OUTDOOR
• TYPICIAL EXAMPLES OUTDOOR :
– EXAMPLE 1 : NO HEATING :
– EXAMPLE 2 : DEW AIR AT AIR OUTLET .
• REASON : DEFROST.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 11


m
CLASSIFICATION OF TROUBLES :
1°/ NO MALFUNCTION- OUTDOOR
• TYPICIAL EXAMPLES OUTDOOR :
– EXAMPLE 1 : NO HEATING :
– EXAMPLE 2 : DEW AIR AT AIR OUTLET .
– EXAMPLE 3 : GAS NOISE .
• REASON :
– A) HOT GAS INJECTION :
» PRESSURE EQUALISATION AT START OF COMPRESSOR TO
REDUCE LOAD MOTOR.
» WHEN A COMPRESSOR STOPS, SYSTEM MUST EQUALISE
BEFORE RESTARTING .
– B) PURGE RECEIVER :
» BEFORE COMPRESSOR STOPS , RECOVER REFRIGERANT TO
LIQUID RECEIVER.
– C) CHANGE OF 4 WAY-VALVE
» DEFROST INITIATION/TERMINATION.
» NEED MINIMUM 3 BAR DIFFERENCE TO MOVE.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 12


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :
• TYPICAL PHENOMENA’S OF A/C OR HEAT-PUMP.

– A MALFUNCTION WITHOUT ERROR INDICATION :


• ABNORMALITY NOT DETECTED BY ANY SENSOR.
• RESULT = GENERALLY CAPACITY SHORTAGE

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 13


m
CLASSIFICATION OF TROUBLES :
2°/ MALFUNCTION WITHOUT ERROR.
• TYPICIAL EXAMPLES :
– RETRY SAFETY DEVICE (PRESSURE,CURRENT,ROTATION):
• BEFORE STOPPING ON ERROR, CONTROL RESTARTS SEVERAL
TIMES TO CONFIRM TROUBLE .
– MALFUNCTION PART WITHOUT DETECTION .
• EXAMPLES :
–SOLENLOID or EXPANSION VALVE MECHANICALLY
CLOSED EVEN COIL ENERGIZED ,
–SOLENOID or EXPANSION VALVE INTERNAL LEAK
INLETOUTLET
–PHASE L2,L3 MISSING DURING OPERATION.⌛ U2,J2.
–OPEN MOTOR-WINDING
» multi-tab (FXLQ/FXNQ/FXDQ/FXSQ/FXMQ) &
» phase-control motor FXFQ/FXZQ .
–CAPILLARY TUBE BLOCKED.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 14


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :
• TYPICAL PHENOMENA’S OF A/C OR HEAT-PUMP.
– A MALFUNCTION WITHOUT ERROR INDICATION :
• ABNORMALITY NOT DETECTED BY ANY SENSOR.
• RESULT = GENERALLY CAPACITY SHORTAGE

– A MALFUNCTION BY SOME INDICATION.


• For SENSOR = out of range ;
• For LIMIT-SWITCH = no change open↔close : multiple cause:
– Float-switch error : faulty float-swich, drain-pump block, faulty relay
control board, lift over max. value, block drain-pipe …
• For PART ; at initialisation ( step motor coil-check ,power supply…)
• RESULT = ERROR INDICATION BY ;
– L.C.D. DISPLAY CONTROLLER.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 15


m
KIND OF ERROR INDICATION
WIRED REMOTE CONTROLLER

ERROR STOPS THERMOSTAT


C9

INDICATION = WARNING-ONLY

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 16


m
INSPECTION & FIELD SETTING WIRED CONTROLLER

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 17


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :
• TYPICAL PHENOMENA’S OF A/C OR HEAT-PUMP.
– A MALFUNCTION WITHOUT ERROR INDICATION :
• ABNORMALITY NOT DETECTED BY ANY SENSOR.
• RESULT = GENERALLY CAPACITY SHORTAGE
– A MALFUNCTION BY SOME INDICATION.
• For SENSOR = out of range ;
• For LIMIT-SWITCH = no change open↔close : multiple cause:
– Float-switch error : faulty float-swich, drain-pump block, faulty relay
control board, lift over max. value, block drain-pipe …
• For PART ; at initialisation ( step motor coil-check ,power supply…)
• RESULT = ERROR INDICATION BY ;
– L.C.D. DISPLAY CONTROLLER.

– Wireless ( Infra-red) remote controller “Q & A” method

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 18


m
KIND OF ERROR INDICATION

WIRELESS REMOTE CONTROLLER

RECEIVER (example FXYFP-K / FXFQ-M )

ACTUAL ERROR CODE SEARCH BY


WIRELESS REMOTE CONTROLLER

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 19


m
METHOD ENTERING ERROR-INSPECTION
WIRELESS REMOTE CONTROLLER
7 1 = ENTER ERROR SEARCH
2 = SEARCH INDOOR UNIT
WHEN 2 BEEPS , GO STEP 3
3 = ENTER SEARCH FIRST CODE
4 = SEARCH FIRST CODE
WHEN 2 BEEPS, GO TO STEP 5
5 = ENTER SEARCH SECOND CODE
6 = SEARCH SECOND CODE
WHEN 1 LONG BEEP =
DISPLAY SHOWS ERROR CODE
7 = HOLD ABOUT 5 SECONDS
= LAST ERROR CODE ERASED.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 20


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :
• TYPICAL PHENOMENA’S OF A/C OR HEAT-PUMP.
– A MALFUNCTION WITHOUT ERROR INDICATION :
• ABNORMALITY NOT DETECTED BY ANY SENSOR.
• RESULT = GENERALLY CAPACITY SHORTAGE
– A MALFUNCTION BY SOME INDICATION.
• For SENSOR = out of range ;
• For LIMIT-SWITCH = no change open↔close : multiple cause:
– Float-switch error : faulty float-swich, drain-pump block, faulty relay
control board, lift over max. value, block drain-pipe …
• For PART ; at initialisation ( step motor coil-check ,power supply…)
• RESULT = ERROR INDICATION BY ;
– L.C.D. DISPLAY CONTROLLER
– Wireless ( Infra-red) remote controller “Q & A” method
– L.E.D. INDICATION OUTDOOR UNIT

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 21


m
KIND OF ERROR INDICATION

OUTDOOR UNIT
By indication LED, search table

Control board

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 22


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :
• TYPICAL PHENOMENA’S OF A/C OR HEAT-PUMP.
– A MALFUNCTION WITHOUT ERROR INDICATION :
• ABNORMALITY NOT DETECTED BY ANY SENSOR.
• RESULT = GENERALLY CAPACITY SHORTAGE
– A MALFUNCTION BY SOME INDICATION.
• For SENSOR = out of range ;
• For LIMIT-SWITCH = no change open↔close : multiple cause:
– Float-switch error : faulty float-swich, drain-pump block, faulty relay
control board, lift over max. value, block drain-pipe …
• For PART ; at initialisation ( step motor coil-check ,power supply…)
• RESULT = ERROR INDICATION BY ;
– L.E.D. INDICATION OUTDOOR UNIT ,OR
– L.C.D. DISPLAY CONTROLLER.
• Multiple-outdoor : back-up operation.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 23


m
CLASSIFICATION OF TROUBLES
• DESCRIBED TROUBLE IS ;
– NOT A MALFUNCTION :

– A MALFUNCTION WITHOUT ERROR INDICATION

– A MALFUNCTION BY SOME INDICATION :


• ERROR CODE CONTAINS 2 DIGITS .
• LEFT DIGIT = “UPPER” DIGIT = GROUP ERROR ,
• RIGHT DIGIT = “LOWER” DIGIT = SPECIFIC ERROR.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 24


m
OVERVIEW DAIKIN ERROR-CODE
0 1 2 3 4 5 6 7 8 9 A H C J E F
2nd

Protection device Faulty Fan interlock Abnorm. Abnorm. Abnorm. heat Air swing AC inp.OC Faulty Heater Faulty or No-load Faulty cap’y set Insufficient Faulty
I Fan mot.
A activ.(gen) indoor PCB drainH2O level Heat-exch.1 exch.2 temp. Mot. lock Err pow suppl electronic overheat. dirty dust operation (indoor ) water humidifier
n Ol. & Oc.
temp. HPctrl/freezeup volt ind exp.valve Collector supply
d Lock
Includ BYC140C
o
o Faulty sens. Transmiss Faulty drain Faulty Faulty Air swing motor Faulty AC input Faulty Faulty Faulty dirt Faulty humidity Faulty tmp. sensor Faulty rad.sensor Faulty high
C sys. (general) H2O level heat-exch.1 temp. heat-exch.2 temp. FanmotOL/OC lock curr. Sens. syst. suct.air disch.air sensor sens. Syst. system pr. switch
indoor

r Error pcb syst. (r.c)


Transmiss err sens. system Sens. Syst. Oc, lock sens. Faulty sens. Syst. temp. tmp. Sens.
Ctrl<->inv Sens.syst. Incorr comb.
Fandrive/contr Fan motor Fandrive/set Front p Sens.syst. Syst.
u
n
i Safety dev. Faulty outd.PCB HPS if Hpsen Low pr. Compr.mot. Compr.Mot. Fan mot. AC input Faulty electronic Cool/heat Pump Abnormal water Activation of loc. Faulty drain H2O Faulty heat
O E High pr.
t activation upp. Limit or Sw.(LPS) OL. Overcurr. OL.OC. OC exp.valve Switch fail OC. Lock tmp. Safety dev. level syst. storage unit
u Earth leak Sw. (HPS)
(general) Lock Lock (4wayvalve)
t
d
o H Faulty sens. Faulty air temp. Faulty pow. Sup. Faulty Compr.mot. Compr.mot. Fan motor Faulty AC Faulty outd. Faulty dsch. Pump OC. Faulty hot H2O Heat
Faulty low Float switch Faulty drain
o Syst. Sens. Sys. Sens. Sys. high pr. Faulty OL. sensor OC.Lock Faulty Ol, Oc. , inp. power air tmp. air tmp. Lock Fault sens. sens. system (local supply) Storage
(general) Damper fail pressure sys. Sens. Syst. faulty lock Sens. Syst. Sens. Syst. Syst. H2O level unit alarm
r Switch switch sens. Syst. Open (if sens. Syst.
sens.syst. Mode2-26)
u
n Abnormal
F Activation Activation Activation Faulty Abn. heat Expansion Abnormal Abnormal Abnormal oil Abnormal
i discharge discharge high oil RWEYQ pressure
common safety safety exchanger (1) Valve faulty suction oil surface level
t prot.dev. pipe temp. In BSVQ-P pressure temp. pressure
device device temp.
sys.Nr.1&2 Syst.No.1 Syst.No.2

Faulty Faulty Faulty Faulty disch.pipe Faulty LP equiv. Faulty suction Faulty heat. Faulty heat. Fault gas Faulty discharge Faulty oil temp. Faulty Faulty oil pressure
pressure current temp. Sens. Sys. sat. temp. Sens. pipe temp. Exch.2 temp. Faulty liq. pipe temp. pressure sens. Sens. Sys. suction
refrigerant exch.1 temp. sensor
J sens. Sys. sensor (open/cl) Sys. Sens.sys. Sens. Syst. pipe temp. sensor Sys. pr.sens.
temp. Sens. Syst. system
(general) system Sens. Sys. system system
Sens.sys.

Faulty INV system Abn.temp. Abn.temp. DC output AC output Equipment (Multi) Electronic Stall prevention Faulty power Faulty
Zero
outdoor

IGBT rise rad. fins OC (moment’y) gen. Input OC thermal sw. (time lag) transmiss.
L Cross error rise in overcurrent transistor
abnromal (trans.) (time lag) INV ↔outd.
L1 phase sw. box (moment’y)
units

Gas short. Missing Faulty Faulty rad. fin (PM) Faulty DC curr. Faulty AC or DC Equip. (Multi) Autocharge Autocharge Replace Replace Replace Faulty cap’y. Set. Auto charge Leak test
ice ph., unbal. Autocharge sw. box tmp. Sens. Syst. Sens. system outp. Curr. Sens. gen. Inp.OC should be judgm. Charge Charge Charge (outd. unit)
P stopped at Almost Not poss
thermal power temp. Sens. Sys. system VRVIII man chg : restarted Finished OK cylinder cylinder cylinder finished
stor. Eqp. supply step 5 BS4 volume chck Wo input add
not pushed “Master” “Slave 1” “Slave 2” charge 2-15
nt poss.

S U Gas shortage Reversed phase Faulty transmiss Faulty transm. Faulty transm. Faulty transm. Faultcomm Faulty Faulty transmiss. Faulty on site In/out. unit Faulty centr.ctrl. Fault comm. Faulty transm. Incorrect wir./pip.
connected Faulty (gen. or Indoor ↔outd. ind. unit ↔ r.c. Ind. units ( mst.↔ ↔ Outd., or transmiss. to/from other sys. setting address not address setting to/from Ind. unit ↔ centr. (wir./pip.
y power sup. No testrun units slv) to/from to/from entered peripheral eq. ctrl. Conn.Err.)
s Volt. heat.stor.unit remote.ctrl.
t system
e
m
system

Centr.eqp. Faulty Faulty Dble set of


VRVII centr.eq.
M Faulty PCB communic. centr.eqpm.
VRVIII to/from connection address
centr.eq.

Faulty circ. Faulty out. Faulty supply air Faulty circ.air Faulty outs.air Faulty r.c. Faulty H2Oleak. Faulty H2Oleak. Faulty dew cond.
O
3 air hum. air hum. temp. temp. Sens. temp.Sens. temp.sens. sensor 1 sensor 2 sensor
t Sens.
Sens. Sens.
h
e
r Faulty
4 humidify Faulty cold Faulty Faulty cold Faulty heated
valve H2O valve heated H2O H2O ht. Exch.
H2Ovalve ht-exch.
other

Supply air Circ.air fan Faulty Faulty


5 fan mot. oc.,ol. motor oc., ol. supply air circ.air INV
INV

General Faulty PCB Abn. ozone Faulty dirt Fault rm air Fault outs. air Fault high volt. Faulty damper Door switch Humidifier High-perfm. Filter Deodorizing Faulty simple
6 error concentr. sensor temp. Sens. temp. sens. system system open element Replacment. catalyzer r.ctrl.
Sys. Syst. replacemt replacement

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 25


m
BRC1E51A7 –4 digits error code - Indoor

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 26


m
BRC1E51A7 –4 digits error code – Outdoor /1

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 27


m
BRC1E51A7 –4 digits error code – Outdoor/2

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 28


m
BRC1E51A7 –4 digits error code – Outdoor/3

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 29


m
BRC1E51A7 –4 digits error code – Outdoor/4

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 30


m
OVERVIEW Air Curtain Biddle Errors

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 31


m
OVERVIEW Air Curtain Biddle Errors

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 32


m
QUESTIONNAIRE WHEN TROUBLE-SHOOTING
? TROUBLE NEW OR EXISTING INSTALLATION ?
? RECENT CHANGE/NEW APPLIANCE ON SITE ?
? WHAT IS ERROR CODE ?
? WHAT IS RESULT OF TROUBLE-FLOWCHART ?
? IF NO ERROR CODE, WHAT IS PHENOMENA ?
? PERSON AFFILIATE/DISTRIBUTOR VISITED SITE ?
? PERFORMANCE DATA SYSTEM ? (CHECKER DATA)
? CURRENT CONDITION SYSTEM ? (RUN OR STOP)
? REPLACEMENT PART ANY RESULT ?
? FAULTY PART AVAILABLE TO RETURN ?
! IF “DOA” OR DESIGN/MANUF.GEN.TROUBLE
! →FIR for NON-Affiliates (FIR = Field Information Report),
! →GIB-input for Affiliates (GIB =Global Information Bank)
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 33
m
METHOD OFF RETRIEVE ERROR-CODE
• ERROR - INDICATION :
– INDOOR :
• INSPECTION MODE :
– LAST OCCURRED ERROR.
– POSSIBLE TO RESET TO “ ØØ” :
» while display error : hold on/off button ↑±5 seconds
• SERVICE MODE :
– LAST 9 ERRORS OCCURRED
– NOT POSSIBLE TO RESET.
– OUTDOOR : MONITORING MODE

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 34


m
OVERVIEW ERROR CODES - INDOOR

C1 Transmiss error fan drive/control pcb


C6 Incorr comb fandriv or incorr set
A8 Error power supply volt to indoor
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 35
m
OVERVIEW ERROR CODES - OUTDOOR SIDE - 1

New
RWEYQ

F9 : expansion valve motor BSVQ-P fautly


www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 36
m
OVERVIEW ERROR CODES - OUTDOOR SIDE - 2

P2 AUTO CHARGE ON HOLD : BS4 “TEST” NOT PRESSED WHEN REQUIRED


P8 AUTO CHARGE REQUIRED TO RESTART ( PRESS BS4 “TEST” ONCE)
P9 AUTO CHARGE FINISHED
PE AUTO CHARGE ALMOST FINISHED
PA REPLACE CHARGE CYLINDER “MASTER”
PH REPLACE CHARGE CYLINDER “SLAVE1”
PC REPLACE CHARGE CYLINDER “SLAVE”
P7 DURING TEST-RUN- REFRIG VOL CALCULTION NOT POSSIBE BECAUSE
VRV3R MANUAL CHARGE WAS MADE BEFORE TEST-RUN
P8 serie PF DURING TEST-RUN REFRIG VOL CACULATION NOT POSSIBLE BECAUSE
NO INPUT FIELD SETTING 2-15

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 37


m
OVERVIEW ERROR CODES - SYSTEM

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 38


m
OVERVIEW ERROR CODES - CENTRAL & HRV

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 39


m
OVERVIEW ERROR CODES – HXHD125A

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 40


m
OVERVIEW ERROR CODES – EKHBV80,140BA

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 41


m
INSPECTION & REPAIR INSTRUCTIONS
• INSPECTION :
– INVERTER
• for COMPRESSOR.
• for FAN MOTOR.
– EXPANSION VALVE MOTOR
– THERMISTOR
– PRESSURE SENSOR
• REPAIR :
– REPLACEMENT INVERTER COMPRESSOR

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 42


m
INSPECTION INVERTER - COMPRESSOR

DIODE MODULE POWER MODULE


www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 43
m
INSPECTION INVERTER - COMPRESSOR

DIODE MODULE POWER MODULE


www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 44
m
INSPECTION INVERTER - COMPRESSOR

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 45


m
INSPECTION INVERTER - COMPRESSOR
DIODE CHECK of DIODE-MODULE VRV-M9
VDC com Ref Result VDC com Ref Result VDC com Ref Result multimeter
P1 J1 O.L. N3 L1 0,5 N3 P1 0,8
P1 J2 O.L. N3 L2 0,5
P1 J3 O.L. N3 L3 0,5 . . . VDC
J1 P1 0,5 L1 N3 O.L. P1 N3 O.L.
J2 P1 0,5 L2 N3 O.L.
J3 P1 0,5 L3 N3 O.L.

DIODE CHECK of POWER MODULE VRV-M


VDC com Ref Result VDC com Ref Result VDC com Ref Result
P2 U O.L. N3 U 0,4 N3 P2 0,8 Com VDC
P2 V O.L. N3 V 0,4
P2 W O.L. N3 W 0,4
U P2 0,4 U N3 O.L. P2 N3 O.L.
V P2 0,4 V N3 O.L.
W P2 0,4 W N3 O.L.

J1
J2
J3

L1,L2,L3 P1 P2 P3 N3 U,V,W
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 46
m
INSPECTION INVERTER – G-COMPR VRV4

www.daikineurope.co
m
INSPECTION INVERTER - G-COMPR VRV4 R

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 48


m
INSPECTION INVERTER - J-COMPR VRV4

www.daikineurope.co
m
INSPECTION INVERTER - J-COMPR VRV4

www.daikineurope.co
m
INSPECTION INVERTER - FAN MOTOR
• STEP 1 :

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 51


m
INSPECTION INVERTER - FAN MOTOR
• STEP 2 :

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 52


m
INSPECTION INVERTER - FAN MOTOR
• STEP 3 :

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 53


m
INSPECTION INDOOR EXPANSION VALVE MOTOR
WHITE
normal reverse RED
Ø1
white white
1
yellow blue Ø3
2
ORANGE
orange orange
PLUG 3 MOTOR
TO blue yellow EXPANSION
PCB 4 VALVE Ø2Ø4
red red YELLOW BLUE
5
brown brown BROWN
6

closed  closed : 2000 pulses


STEP ( ± 5 msec)
COIL (4) 1 2 3 4 (1)
on
Ø 1 off
on
Ø 2 off
on
Ø 3 off
on
Ø 4 off

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 54


m
“RESET” INDOOR EXPANSION VALVE MOTOR

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 55


m
INSPECTION OUTDOOR EXPANSION VALVE MOTOR
1 COIL = 46 OHM
normal reverse ORANGE
orange orange
1 Ø1
2 red black

PLUG 3 yellow yellow


MOTOR
Ø3
YELLOW
TO black red EXPANSION
PCB 4 VALVE
5 RED Ø 2 Ø 4 BLACK
grey grey
6

GREY
12VDC
31.25 PULSE PER SECOND closed  closed : 480 pulses
1 PULSE = 32 msec.

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 56


m
INSTRUCTION FOR EXPANSION VALVE BODY

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 57


m
INSPECTION AIR & HEX. THERMISTOR

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 58


m
INSPECTION THERMISTOR - DISCHARGE

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 59


m
INSPECTION PRESSURE SENSORS

HP

HP

LP
LP

www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 60


m
INSTRUCTION FOR REPLACEMENT
INVERTER COMPRESSOR VRVII
1°/ RECOVER REFRIGERANT (MODE 2 - CODE 21)
2°/ REMOVE SOUND INSULATION & POWER TERMINALS
3°/ CUT PIPES BETWEEN BRAZING & COMPRESSOR
4°/ HEAT-UP PIPE AND PULL OUT ORIGINAL PIECE
5°/ REMOVE BOLTS & COMPRESSOR .
6°/ POSITION NEW COMPRESSOR
7°/ TAKE OUT CAPS (INSIDE N2)
8°/ BRAZE ALL PIPES :
8.1 ! N2 FLOW ( MAX. 0.02MPa)
8.2 ! COOL OIL EQUALIZING SEAT!
9°/ LEAK TEST.
10°/ VACUUM DRYING.
11°/ REFRIGERANT CHARGE :
11.1 WITHOUT COMPRESSOR OPERATION
11.2 WITH COMPRESSOR OPERATION : MODE 2 - CODE 20.
12°/ CONFIRM VOLTAGE & CURRENT IS EQUAL TO U/V/W .
www.daikineurope.co S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING" P. 61
m
www.daikineurope.co P. 62
S-V04 – VRV IV - CHAPTER 6 "TROUBLESHOOTING"
m