Professional Documents
Culture Documents
MEK10503
MEK10503
1
Introduction
Types of Abnormalities
Short circuits
- causes of SC including failure of insulation due to
* excessive moisture,
* mechanical damage to electrical distribution
equipment,
* failure of utilization equipment as a result of
overloading or other abuse.
SC may occur between
- two phase conductors
- between all phases of a polyphase system, or
- between one or more phases and ground.
MKE 1193 – Electric Power Systems Protection
5
Introduction
Dependability
A relay is said to be dependable if it trips only when it
is expected to trip.
Dependability is the degree of certainty that the relay
will operate correctly. (Operated dependably when
fault conditions occur, even after remaining idle for
months or years).
Dependability can be improved by increasing the
sensitivity of the relaying scheme.
Sensitivity
Sensitivity is the ability of the relay to pick up even on
the smallest possible faults.
Reliability
It is the ability to ’not to fail’ in its function.
It can be achieved by redundancy.
Redundancy in protection depends on the criticality of
the apparatus.
Reliability can be improved by providing backup
protection.
Selectivity
It is the ability to correctly locate and classify the fault.
A relay should be able to discriminate whether the
fault is in its jurisdiction or not.
This jurisdiction of a relay is called zone of protection.
Protection zones are classified into primary and
backup zones.
Speed
A fault should be cleared as quickly as possible in
order to :
Maximize safety
Minimize equipment damage
Minimize system instability
The relay should quickly arrive at a decision and
circuit breakers should be fast enough.
1 2
CB Fault CB
T R12 T R21
R R
What is Relay?
A relay is a logical element which process the
inputs (mostly voltages and currents) from the
system and issues a trip decision if a fault within
its jurisdiction is detected.
Inputs to a relay are:
Current from a current transformer.
Voltage from a voltage transformer.
Evolution of Relay technologies:
Early 1900s – electromechanical relays
Late 1950s – solid-state relays
1980s – microprocessor relays
MKE 1193 – Electric Power Systems Protection
16
Relays
Electromechanical Relays
First generation of relays.
Uses the principle of electromechanical energy
conversion.
Immune to electromagnetic interference and
rugged.
source
Is
Is5
Is4
Is3
Is2
5 4 3 2 1 Distance
MKE 1193 – Electric Power Systems Protection
21
Overcurrent Relays
t1
source
5 4 3 2 1
I
Primary conductor
I’
+
E’ Xe Ie ZB
-
1:n
CT equivalent circuit
Current Ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5
450:5 500:5 600:5 800:5 900:5 1000:5 1200:5
1500:5 1600:5 2000:5 2400:5 2500:5 3000:5 3200:5
4000:5 5000:5 6000:5
MKE 1193 – Electric Power Systems Protection
29
Introduction
Types of protection
Apparatus protection
Transmission line protection
Transformer protection
Generator protection
Motor protection
Busbar protection
System protection
Out-of-step protection
Under-frequency relays
Islanding systems
Rate of change of frequency relays
MKE 1193 – Electric Power Systems Protection
30
Apparatus Protection
B1 B2 B3
F2 F1
275 kV/33 kV
L1 L2 L3
Example:
Consider the radial system shown in figure below.
Calculate the fault currents for faults FA, FB, FC, FD,
and FE. Propose relay settings on the basis of current
grading, assuming a 50% relay error margin.
4 3 2 1
13.8 kV
FE FD FC FB FA
X5 = 0.5 X43 = 0.25 X32 = 0.05 XT = 2.1
Solution:
The system voltage is 13.8 kV, hence the phase fault
current is
13.8kV
I f (1 )
Xf 3
where Xf is the reactance from the source to the fault
points.
B CT
CT I
A
F2 F1
1 2
D OC
VT
Not
Trip Trip!
Phase A
Phase B
breaker
Phase C trip coil
Distance Protection
The basic principle is that the apparent impedance
seen by the relay reduces drastically in case of line
fault.
If the ratio of apparent impedance to the positive
sequence impedance is less than unity, it indicates a
fault.
This protection scheme is inherently directional.
Impedance relay and Mho relay use this principle.
Distance Protection
F1 F2
ZR
BLOCK
normal
TRIP operation
R=Re(Z)
I Protected I
Apparatus
Relay
i1 i1-i2 i2
Zone 4 Zone 7
Zone 2 Zone 9
Zone 1 Zone 5 Zone 8
CT3 I3
CT2 I2 F
Example:
Consider a /Y-connected, 15 MVA, 33/11-kV transformer with
differential protection applied, for the current transformer ratios shown
in figure. Calculate the relay current on full load. Find the minimum
relay current setting to allow 125% overload.
33/11 kV
300/5 A 2000/5 A
ip is
ir Relay
Solution: