Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 56

MEK 10503

Power System Protection

1
Introduction

Why do we need protection?


To limit the consequences of a fault (damage
asset).
Reduce the risks to acceptance levels while
maintaining the disruption to operation of the
power system. (to ensure maximum continuity of
electrical supply with minimum damage to life,
equipment, and property)
Safety of human personnel

MKE 1193 – Electric Power Systems Protection


2
Introduction

The consequences of un-cleared faults


Abnormally large currents are caused to flow in parts
of the system with the associated overheating of
components.
System voltages will be off their normal acceptable
levels, resulting in possible equipment damage (under
voltages/ over voltages condition).
Parts of the system will be caused to operate as
unbalanced three-phase systems, which will mean
improper operation of the equipment. (i.e. lose
synchronism)

MKE 1193 – Electric Power Systems Protection


3
Introduction

Protection design approach


Quickly isolate the affected portion of the system and
to maintain normal service for the system for the rest
of the system. This isolation also minimizes damage
to the affected portion of the system.
Minimize the magnitude of the available short-circuit
current and, in this manner, minimize potential
damage to the system, its components, and the
utilization equipment it supplies
Provide alternate circuits, automatic transfers,
automatic reclosing/automatic transfer devices, where
applicable, in order to minimize the duration or the
extent of supply and utilization equipment outages.
MKE 1193 – Electric Power Systems Protection
4
Introduction

Types of Abnormalities
Short circuits
- causes of SC including failure of insulation due to
* excessive moisture,
* mechanical damage to electrical distribution
equipment,
* failure of utilization equipment as a result of
overloading or other abuse.
SC may occur between
- two phase conductors
- between all phases of a polyphase system, or
- between one or more phases and ground.
MKE 1193 – Electric Power Systems Protection
5
Introduction

The requirements (desirable attributes) for


protective power systems design criteria are:
Dependability
Reliability
Selectivity
Speed
Economy
Simplicity

MKE 1193 – Electric Power Systems Protection


6
Introduction

Dependability
A relay is said to be dependable if it trips only when it
is expected to trip.
Dependability is the degree of certainty that the relay
will operate correctly. (Operated dependably when
fault conditions occur, even after remaining idle for
months or years).
Dependability can be improved by increasing the
sensitivity of the relaying scheme.
Sensitivity
Sensitivity is the ability of the relay to pick up even on
the smallest possible faults.

MKE 1193 – Electric Power Systems Protection


7
Introduction

Reliability
It is the ability to ’not to fail’ in its function.
It can be achieved by redundancy.
Redundancy in protection depends on the criticality of
the apparatus.
Reliability can be improved by providing backup
protection.

MKE 1193 – Electric Power Systems Protection


8
Introduction

Selectivity
It is the ability to correctly locate and classify the fault.
A relay should be able to discriminate whether the
fault is in its jurisdiction or not.
This jurisdiction of a relay is called zone of protection.
Protection zones are classified into primary and
backup zones.

Distance or Over-current Protection Scheme


MKE 1193 – Electric Power Systems Protection
9
Introduction

Selectivity is usually provided by


Time discrimination. Over-current and distance use
this principle.
Applying differential protection principle. In the case of
differential protection, the CT location provides crisp
demarcation of zone of protection.

Differential Protection Scheme

MKE 1193 – Electric Power Systems Protection


10
Introduction

Speed
A fault should be cleared as quickly as possible in
order to :
 Maximize safety
 Minimize equipment damage
 Minimize system instability
The relay should quickly arrive at a decision and
circuit breakers should be fast enough.

MKE 1193 – Electric Power Systems Protection


11
Introduction

Speed vs. Accuracy


The consequences of quick tripping decisions are:
 Nuisance tripping or tripping when there is no fault.
 Tripping for faults outside the relay jurisdiction.
 High-speed system tend to be less accurate because of
lesser amount of information.

Figure 1.3 Conceptual illustration of Speed vs. Accuracy Conflict

MKE 1193 – Electric Power Systems Protection


12
Components of Protective Schemes

1 2

CB Fault CB

T R12 T R21

R R

Circuit Breaker (CB) – to open the line


Transducers (T) – to provide low-level current and
voltage samples to the relay (Instrument transformers)
Relay (R) – to process the current and voltage signals to
produce binary logic signal – ‘trip’ or ‘block’
MKE 1193 – Electric Power Systems Protection
13
Circuit Breaker

What is a circuit breaker ?


A circuit breaker is basically a switch to interrupt
the flow of current.
It is a device , when received fault signal from
relays, will open the faulted section circuit.
It has to handle large voltages and currents.
The inductive nature of power system results in
arcing between the terminals of a CB.

MKE 1193 – Electric Power Systems Protection


14
Circuit Breaker

High voltage circuit breakers, 11 kV and above,


take 5 basic forms: oil immersed, air blast, small
oil volume, sulphur hexafluoride (SF6), and
vacuum.
The common symbols:

MKE 1193 – Electric Power Systems Protection


15
Relays

What is Relay?
A relay is a logical element which process the
inputs (mostly voltages and currents) from the
system and issues a trip decision if a fault within
its jurisdiction is detected.
Inputs to a relay are:
Current from a current transformer.
Voltage from a voltage transformer.
Evolution of Relay technologies:
Early 1900s – electromechanical relays
Late 1950s – solid-state relays
1980s – microprocessor relays
MKE 1193 – Electric Power Systems Protection
16
Relays

Electromechanical Relays
First generation of relays.
Uses the principle of electromechanical energy
conversion.
Immune to electromagnetic interference and
rugged.

MKE 1193 – Electric Power Systems Protection


17
Relays

The benefits of microprocessor relay:


Lower costs than electromechanical relays
Fault-location capability with local and remote
reporting
Space saving
Event-recording capability
Reliable, with self-checking capability
Flexible applications, both in programming and
protection capability.
Short delivery time
Simple (in terms of panel layout, wiring, and setting
process)
Reduced engineering and drafting requirements
MKE 1193 – Electric Power Systems Protection
18
Overcurrent Relays

Very high current is usually caused by fault.


Common protection devices for overcurrent
phenomenon in power system:
Thermo-magnetic switches
Moulded-case circuit breakers (MCCBs) Low voltage
applications
Fuses only!
Overcurrent relays
Types of overcurrent relays:
Definite-current relays
Definite-time relays
Inverse-time relays

MKE 1193 – Electric Power Systems Protection


19
Overcurrent Relays

Definite-current relay operates when the current


reaches a predetermined value.

MKE 1193 – Electric Power Systems Protection


20
Overcurrent Relays

Setting for definite-current relay:


Low current at the substation furthest away from
the source and progressively increased moving
towards the source.
5 4 3 2 1

source

Is
Is5
Is4
Is3
Is2
5 4 3 2 1 Distance
MKE 1193 – Electric Power Systems Protection
21
Overcurrent Relays

Definite-time relay operates according to the


pre-set operating time. It is connected with a
timer. The protection is more selective.

t1

MKE 1193 – Electric Power Systems Protection


22
Overcurrent Relays

Setting for definite-time relay:


The breaker nearest to the fault is tripped in the
shortest time.
5 4 3 2 1

source

1.5 1.0 0.5 0.25


Time 1.5 sec
1.0 sec
0.5 sec
0.25 sec

5 4 3 2 1

MKE 1193 – Electric Power Systems Protection


23
Overcurrent Relays

Inverse-time relay operates in a time that is


inversely proportional to the fault current. The
larger the measured fault current in relation to
the operating value, the faster the relay trips.

MKE 1193 – Electric Power Systems Protection


24
Instrument Transformers

I
Primary conductor

I’

+ Current transformer (CT)


+
V V’
-
-
Voltage transformer (VT)

2 basic types of instrument transformers:


Voltage transformers (VTs) or Potential transformer
(PT)
Current transformers (CTs)
MKE 1193 – Electric Power Systems Protection
25
Instrument Transformers

MKE 1193 – Electric Power Systems Protection


26
Instrument Transformers

Voltage or Potential Transformers (VT or PT) – To


provide a voltage which is much lower than the system
voltage. The secondary voltage should be as near as
possible proportional to the primary voltage. The nominal
secondary voltage being 120 VLL or 69 VLN. Provide
voltage for standardize levels of relay operation level.
Current Transformers (CT) – To obtain currents which
are proportional to the system (primary) currents, and
which can be used in control circuits. The protection
current transformers must remain accurate up to at least
20 times normal full load. Provide current for standardize
levels of relay operation level.

MKE 1193 – Electric Power Systems Protection


27
Instrument Transformers

VTs are generally modelled as an ideal


transformer:
1
V ' V
n

Standard secondary voltage rating = 120 V LN.


Standard VT ratios:
Voltage Ratios
1:1 2:1 2.5:1 4:1 5:1 20:1 40:1
60:1 100:1 200:1 300:1 400:1 600:1 800:1
1000:1 2000:1 3000:1 4500:1

MKE 1193 – Electric Power Systems Protection


28
Instrument Transformers

The normal current rating of CT secondary is


standardized at 5 A in the US, and 1 A in Europe.
I (I’+Ie) I’
Z’

+
E’ Xe Ie ZB
-

1:n
CT equivalent circuit

Current Ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5
450:5 500:5 600:5 800:5 900:5 1000:5 1200:5
1500:5 1600:5 2000:5 2400:5 2500:5 3000:5 3200:5
4000:5 5000:5 6000:5
MKE 1193 – Electric Power Systems Protection
29
Introduction

Types of protection
Apparatus protection
Transmission line protection
Transformer protection
Generator protection
Motor protection
Busbar protection
System protection
Out-of-step protection
Under-frequency relays
Islanding systems
Rate of change of frequency relays
MKE 1193 – Electric Power Systems Protection
30
Apparatus Protection

Principle of Over-current Protection


When the current in a system exceeds a
predetermined value, it indicates the presence of a
fault.
Relaying decision is based solely on the magnitude of
current.
Used in radial distribution systems.
Over-current relaying and fuse protection uses this
principle. 1 2 3

B1 B2 B3

F2 F1
275 kV/33 kV

L1 L2 L3

MKE 1193 – Electric Power Systems Protection


31
Radial System Protection

Consider fault at F1. Circuit breaker B3 will open


first and B2 and B1 remain closed as longer time
delay is selected for B2 and B1. Under this
condition, only load L3 is interrupted. Only if B3
fails to open will B2 open.
Consider fault at F2. B2 will open to cause L2
and L3 interrupted. B1 is selected with longer
time delay as a backup to B2.
B2 provides primary protection for fault at F2 as
well as backup for fault at F1. B1 provides
primary protection for fault between B1 and B2
as well as backup for further downstream faults.
MKE 1193 – Electric Power Systems Protection
32
Radial System Protection

Example:
Consider the radial system shown in figure below.
Calculate the fault currents for faults FA, FB, FC, FD,
and FE. Propose relay settings on the basis of current
grading, assuming a 50% relay error margin.

4 3 2 1
13.8 kV

FE FD FC FB FA
X5 = 0.5  X43 = 0.25  X32 = 0.05  XT = 2.1 

MKE 1193 – Electric Power Systems Protection


33
Radial System Protection

Solution:
The system voltage is 13.8 kV, hence the phase fault
current is
13.8kV
I f (1 ) 
Xf 3
where Xf is the reactance from the source to the fault
points.

For fault FA,


X fA  0.5  0.25  0.05  2.1  2.9 .
13.8kV
 I fA   2747.39 A.
2.9 3
MKE 1193 – Electric Power Systems Protection
34
Radial System Protection

For fault FB,


X fB  0.5  0.25  0.05  0.8 .
13.8kV
 I fB   9959.29 A.
0.8 3
For fault FC,
X fC  0.5  0.25  0.75 .
13.8kV
 I fC   10623.25 A.
0.75 3
Since FD is very close to FC, then
IfD = IfC = 10623.25 A.

MKE 1193 – Electric Power Systems Protection


35
Radial System Protection

For fault FE,


X fE  0.5 .
13.8kV
 I fE   15934.87 A.
0. 5 3
The relay at 1 should respond to faults FB and FC and
should be set at 150% of fault current at FA. Thus,
IS1 = 1.5 IfA = 4121.09 A.

The relay at 2 should respond to faults FE and FD and


should be set at
IS2 = 1.5IfC = 15934.88 A.
MKE 1193 – Electric Power Systems Protection
36
Apparatus Protection

Directional Over-current Protection


Uses both magnitude of current and phase angle
information for decision making.
Used in radial distribution systems with source at both
ends.

A Radial System with Source at Both Ends

MKE 1193 – Electric Power Systems Protection


37
Directional Relays

Designed to operate for fault currents in only


one direction.
C CT

B CT

CT I
A
F2 F1
1 2
D OC
VT
Not
Trip Trip!
Phase A

Phase B
breaker
Phase C trip coil

MKE 1193 – Electric Power Systems Protection


38
Apparatus Protection

Distance Protection
The basic principle is that the apparent impedance
seen by the relay reduces drastically in case of line
fault.
If the ratio of apparent impedance to the positive
sequence impedance is less than unity, it indicates a
fault.
This protection scheme is inherently directional.
Impedance relay and Mho relay use this principle.

Fault on Transmission Line


MKE 1193 – Electric Power Systems Protection
39
Apparatus Protection

Distance Protection

Impedance Relay Characteristics A Mho Relay


in R-X plane

MKE 1193 – Electric Power Systems Protection


40
Line Protection with Distance Relays

Distance relay also called as impedance relay. It’s


function is depends on the impedance measured.
A B

F1 F2

Relay at A uses the line current and the line


voltage to evaluate Z = V/I. The value of the
impedance Z for a fault at F1 would be ZAF1, and
(ZAB + ZBF2) for a fault at F2.
MKE 1193 – Electric Power Systems Protection
41
Line Protection with Distance Relays

Impedance relay block and trip regions are given


in a R-X plane:
X=Im(Z)

ZR
BLOCK
normal
TRIP operation

R=Re(Z)

MKE 1193 – Electric Power Systems Protection


42
Apparatus Protection

Principle of Differential Protection


It is based on the fact that any fault within an
electrical equipment would cause the current entering
it to be different from the current leaving it.
By comparing the two currents either in magnitude or
in phase or in both, fault can be determined.
It is an attractive option if both the ends of the
apparatus are located near each other.

Fault on Transmission Line


MKE 1193 – Electric Power Systems Protection
43
Differential Relays

Differential protection system is use to prevent


short circuit between different phases in a system.
Differential relays are commonly used to protect
generators, buses, and transformers.

I Protected I
Apparatus

Relay
i1 i1-i2 i2

MKE 1193 – Electric Power Systems Protection


44
Zones of Protection

In general power system configurations, a


fundamental protection concept is the division of
a system into protective zones. Zones are
defined for:
Generators
Transformers
Buses
Transmission lines
Motors

MKE 1193 – Electric Power Systems Protection


45
Zones of Protection

Protective zone concept:

Zone 4 Zone 7

Zone 2 Zone 9
Zone 1 Zone 5 Zone 8

Zone 3 Zone 6 Zone 10

MKE 1193 – Electric Power Systems Protection


46
Zones of Protection

Protective zones have the following


characteristics:
Zone are overlapped
Circuit breaker are located in the overlap regions
For a fault anywhere in a zone, all circuit breakers in
that zone open to isolate the fault

MKE 1193 – Electric Power Systems Protection


47
Generator Protection

Generator Main circuit


stator windings breaker contacts
C
Generator
neutral breaker
B
I1 CT CT I2
A

I’1 - I’2 Relay


I’1 operating I’2
coil
R R
Relay
restraining
coils

MKE 1193 – Electric Power Systems Protection


48
Generator Protection

Differential protection system is use to prevent


short circuit between different phases of the
generator winding.
In the case of no internal fault within the
generator windings, I1 = I2, and thus I’1 - I’2 = 0.
The relay will operate whenever there is an
internal fault occurred, I1 ≠ I2 and I’1 ≠ I’2. Since
this relay operation depends on a difference
current, it is called a differential relay.

MKE 1193 – Electric Power Systems Protection


49
Bus Protection

Buses are usually protected against fault


conditions using the differential relay. The
differential bus protection is illustrated as follows:
I1 bus
CT1

CT3 I3

CT2 I2 F

I’1 + I’2 - I’3


Relay
operating
I’2 coil
R
I’1 I’3
R R
Relay
restraining
coils
MKE 1193 – Electric Power Systems Protection
50
Bus Protection

For the case of no bus fault, I1 + I2 = I3 and the


differential relay current I’1 + I’2 – I’3 = 0, the relay
does not operate.
If there is a bus fault, the differential current
becomes non-zero and the relay operate.

MKE 1193 – Electric Power Systems Protection


51
Transformer Protection

A number of fault conditions can arise within a


power transformer, including:
Earth faults
Core faults due to insulation breakdown
Interturn faults due to winding flashover
Phase-to-phase faults (rear)
Tank faults resulting in loss of oil reduce winding
insulation
Overheating protection is provided for
transformers by placing a thermal-sensing
element in the transformer tank.
MKE 1193 – Electric Power Systems Protection
52
Transformer Protection

Overcurrent relays are used as a backup


protection.
Differential protection is the main scheme used
for transformer.

MKE 1193 – Electric Power Systems Protection


53
Transformer Protection

Example:
Consider a /Y-connected, 15 MVA, 33/11-kV transformer with
differential protection applied, for the current transformer ratios shown
in figure. Calculate the relay current on full load. Find the minimum
relay current setting to allow 125% overload.
33/11 kV

300/5 A 2000/5 A

ip is

ir Relay

MKE 1193 – Electric Power Systems Protection


54
Transformer Protection

Solution:

The primary line current is


15 x106
IP  3
 262.43 A
3 (33 x10 )

The secondary line current is


15 x106
IS  3
 787.30 A
3 (11x10 )
The C.T. current on the input side is
 5 
iin _ s (CT )  262.43   4.37 A.
 300 
MKE 1193 – Electric Power Systems Protection
55
Transformer Protection

The C.T. current on the output side is


 5 
iout _ s (CT )  787.30  3  3.41A.
 2000 
The relay current on full load is
ir  iin _ s (CT )  iout _ s (CT )  4.37  3.41  0.9648 A

With 125% overload, the minimum relay current setting should be


ir  (1.25)(0.9648)  1.206 A.

MKE 1193 – Electric Power Systems Protection


56

You might also like