Professional Documents
Culture Documents
Elect MC 1 Chap-2 Lecture-5
Elect MC 1 Chap-2 Lecture-5
Elect MC 1 Chap-2 Lecture-5
Chapter –1 ( Transformer )
Lecture No.5
1
Chapter –2 ( Transformer )
2.5 Equivalent Circuit of Real Transformer:
It is seen that the net magnetic flux remains constant, it does not depend on the load current I 2
and it only depends on no-load current. In order to satisfy these physical conditions of the
transformer, the equivalent circuits of the transformer without load and with load are
developed as shown in Fig.2.9 and Fig.2.10 respectively.
2
V1 = Input voltage
E1 = Emf induced across the P.W.
E2 = Emf induced across the S.W.
V2 = Load terminal voltage (< E2 )
I0 = No-load primary current (remains constant)
I2 = Load current = S.W. current (Varies with load)
I2’ = Additional current in primary P.W. due to load
on secondary side.
R1 = Resistance of P.W.
X1 = Leakage reactance of P.W. Fig.2.10 Detail Equivalent circuit of transformer
R2 = Resistance of S.W.
~ ~ ~
X2 = Leakage reactance of S.W. V I ' .( R jX ) E Since I0 is << I2’ , I1 ≈ I2’
1 2 1 1 1
R0 = Shunt branch core loss resistance ~ ~ ~
Therefore V I .( R jX ) E (approximately) (2.11)
X0 = Shunt branch magnetizing reactance 1 1 1 1 1
Iw = V1/ R0 = In phase component of I0 ~ ~ ~
Iμ = V1/ R0 = 90 lagging component of I0
0 And V E I .( R jX ) (2.12)
2 2 2 2 2
Iw 2 R0 = Iron loss (core loss)
Iμ 2 X0 =Reactive power consumes by transformer
to produce magnetic flux in the core
Z ( R jX ) Series Impedance of primary winding
1 1 1
Z ( R jX ) Series Impedance of secondary winding
2 2 2
3
The physical significance of leakage reactance can be explained with the help of Fig.2.12.
The primary winding current produces magnetic flux in the core. Out of the total flux
produced by the primary current, major part of the flux () passes through the iron core
and links with the secondary winding. However, a small amount of flux leaks through
the air path locally and links with only the primary winding. This flux is known as
primary leakage flux and denoted by ‘ l1’.
4
The emf E1 induced in the primary winding opposes
the supply voltage V1 and it is proportional to the main
flux and does not depend on load currents. i.e E 1
remains constant.
5
2.5 Transformation of Impedance :
The equivalent circuit shown in Fin.2.10
further can be simplified by transferring the
resistance and leakage reactance of the
secondary winding to the primary side as as
shown in Fig.2.13
R2 is transferred to primary side with a new Fig.2.10 Detail Equivalent circuit of transformer
value R2’ in such a way that R2’ produces same
amount of power loss in primary side as it
produces in the secondary side. R 2’ is known
as equivalent of R2 referred to primary side.
(I2’)2 R2’ = (I2)2 R2 (Assuming I1≈ I2’ ) Fig.2.13 Equivalent circuit of transformer
2 referred to primary side
I
'
OR R 2
(I1)2 R2’ = (I2)2 R2 2 I 2
.R
1
I 2 N1 1
But R' 1 .R (2.16)Similarly X ' 1 . X (2.17)
I1 N 2 K 2 K2 2 2 2
K2
6
Now final equivalent circuit of the transformer referred to primary side can be written as
shown in Fig.2.14. Here, Load impedance and load voltage also has been transferred to
primary side.
R01 = R1 + R2’ = Total series resistance of the transformer referred to primary side
X01 = X1 + X2’ = Total series reactance of the transformer referred to primary side
Z R 2 X 2 = Total series Impedance of the transformer referred to primary side
01 01 01
Z
Z ' L Equivalen t of load impedance refer to primary side
L K2
V
V ' 2 Equivalent of load voltage refer to primary side
2 K
7
The equivalent circuit also can be developed by transferring the resistance and leakage reactance
of the primary winding to the secondary side as shown in Fig.2.15.
8
Now final equivalent circuit of the transformer referred to secondary side can be written as
shown in Fig.2.16. Here, input voltage V 1, I0 and Iμ also has been transferred to secondary side.
Solution:
The phasor diagram at no-load is shown below:
V1 2200
X0 4691 Ohms
I 0.469
10
Illustrative example2.3:
A step-up single phase transformer supplies a current of 5 amp to the load at 200V at 0.8
lagging power factor. R1 = 0.5 ohm, X1 = 1 ohm, R2 = 2 ohm, X2 = 4 ohm, R0= 400 ohms, X0
= 240 ohms, turn ratio N2/N1 = 2. Find V1, I1 and input power factor.
Solution:
The equivalent circuit of the transformer is shown below:
~ ~
Let V be the reference phasor, i.e. V 20000
2 2
~
I2 lags V2 by 2, where 2 = Cos-1(0.8) = 36.870 I 5 36.870
2
~ ~ ~
E V I .( R jX ) = 20000 + (5-36.870).(2+j4)
2 2 2 2 2
~
OR E 20000 (5 - 36.870 ) (4.47263.430 ) 220.22.60
2
11
~' ~ N
I I 2 10 36.87 0
2 2 N
1
~ ~ N
E E 1 110 .12.6 0
1 2 N
2
~ ~ ~
And V E I ' .( R jX ) 1102.60 (10 - 36.870 ).(0.5 j1)
1 1 2 1 1
~
V 120.294.70
1
~
~ V1 120.294.70 ~ V1 120.294.70
I 0.501 85.30 IW 0.34.70
X0 24090 0
R0 400
~ ~ ~
I I I (0.34.70 ) (0.501 - 85.30 ) 0.5825 - 54.530
0 W
~ ~ ~
I I I ' ( 10 - 36.870 ) + (0.5825 - 54.530 ) 10.548 - 37.530
1 0 2
~ ~
Phase Angle between V and I 4.70 - (-37.530 ) 42.230 I~ Lags V~ by 42.230
1 1 1 1 1
Hence, input power factor = Cos(42.23 0) = 0.74 lagging
12
Power Losses and Efficiency of Transformer:
- The input power of the transformer is equal to V 1I1Cos1
ii) Copper loss: When the transformer is loaded, current flows through primary winding as
well as secondary winding. The internal resistance of the primary winding and the secondary
winding produces heat due to current flowing through them. The power loss due to the heat so
produced is known as copper loss. The magnitude of copper loss depends upon the square of
current and can be calculate as follow:
Total copper loss = Copper in PW + Copper in SW = I 12 R1 + I22 R2 ( 2.21)
OR Total copper loss = = I12 R01 = I22 R02 (watts)
14
It is clear from the eqn (2.21) that the copper loss of the transformer varies with the load
current. Hence, it is also known as variable loss.
Input power is given by: Pin = V1I1Cos1
Output power: Pout = Pin – Iron loss – Copper loss = V1I1Cos1 – Wi – I12 R01
Pout Pout
Efficiency of transformer pu. Or η 100 %
Pin Pin
V1 .I1 Cos1 - Wi - I12 R01
OR η (2.22)
V1 .I1 Cos1
From the eqn (2.22), it is clear that the efficiency of transformer varies with the load
current. At no-load, output power is zero and input power is V 1I0Cos0 = Wi. Hence, the
efficiency is zero at no-load. When the load goes on increasing, the output power goes on
increasing and efficiency also increases accordingly.
However, there is a limit on increasing the efficiency. At a particular value of load current,
the efficiency becomes maximum. Further increased in load beyond this value will cause
decrease in efficiency.
At which particular value of load current, the efficiency will be maximum can be
determined as follow:
15
V1.I1 Cos1 - Wi - I12 R01
η (2.22)
V1.I1 Cos1
OR Wi I12 R01 Wi
OR when I1 (2.23)
R01
Wi
Hence, efficiency will be maximum at I1 OR when Iron loss Copper loss
R01
N V
Transforma tion ratio K 2 2 2
N V
1 1
R2, X2 and RL can be transferred to the primary side as follow:
R X R
0.1 2 0.4 0.1 R' L 10 2.5
R' 2 0.025 X' L
2 2 2 2
K 2 22 K 2 22
K 2
17
Hence, the equivalent circuit referred to primary side can be written as follow:
Input power Pin = Pout + Copper loss + Iron loss = 4840 + 145 + 30.35 = 5015.25 W
Pout 4840
Hence efficiency 100 100 96.5%
Pin 5015.25
18