Professional Documents
Culture Documents
Chater 2 Transformers
Chater 2 Transformers
Chater 2 Transformers
Electrical Machines
ECEG-3203
Chapter 2
shell types
Shell type transformer
t
The rms value of the induced voltage hence is
The noload resistance drop is very small and the counter emf (e1)
is very nearly equal to the applied voltage (V1)
im I sin c
ic I cos c
The core loss PC is therefore
therefore
N1
a
N2
The side the shunt branch parameters should be placed is
determined by to which side of the transformer is the measurment
conducted.
| vnoload | | vload |
x100
| vload |
Vno-load =RMS voltage across the load terminals without load
Vload = RMS voltage across the load terminals with a specified
load
V2 I 2Cos 2
*100
Losses V2 I 2Cos 2
V2 I 2Cos 2
2 2 2
*100
V1 / Rc1 I1 R1 I 2 R2 V2 I 2Cos 2
V2 I 2Cos 2
2 2
*100
V1 / Rc1 I 2 Req 2 V2 I 2Cos 2
100 pf=1
pf= 0.8
pf= 0.6
At this load current
core loss = copper loss
0
Definition:
The transformer vector group show the phase difference
between the primary and secondary sides of the transformer.
It also determines the high voltage and low voltage windings
arrangement of three phase transformers.
•The vector for the high voltage winding is taken as the reference
vector. Displacement of the vectors of other windings from the
reference vector, with anticlockwise rotation, is represented by the
use of clock hour figure.
Source: “Electrical Machinery”, A.E. Fitzgerald, Umans
Cont’d…
The value of VAbase must be the same over the entire system
under analysis. Usually the rated values of the transformer are
taken as base values.
For a single-phase system,
Pbase, Qbase, VAbase = VbaseIbase
Rbase, Xbase, Zbase = Vbase/Ibase
The procedure for per unit analysis can be summarized as