IAC3

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 9

IAC 3

Main Motor Specification

Rated Power : 325 KW


Rated Voltage : 6.6 KV ±10%
Frequency : 50 Hz ±5%
Rated speed : 2981 RPM
Full load current : 30.5 A
No load current : 7 A
Temperature rise over ambient air 50 DEG. C. : 70
DEG.C
Auxiliary oil pump motor specification

Rated Power : 1.5 KW


Rated Voltage : 415 V ±10%
Frequency : 50 Hz ±5%
Rated speed : 1415 RPM
Rated current : 3.2 A
POWER SUPPLY SCHEME
The 3 phase 6.6 kV 50 Hz power supply to
compressor motor is given through the starter panel
which is separate from the compressor control panel.
IAC1 & PAC1 supplied from station 1 OCA
switchgear
IAC2 supplied from station 1 OCB switchgear
IAC3 supplied from station 2 OCC switchgear
PAC2 supplied from station 2 OCC switchgear
Compressor local control panel supplied from
service building which taken from ODB PCC
local control panels
The local control panels considered are micro-
controller based.
Individual control panel will receive various analogue
& digital signals from within the compressor
package. In addition, it will also receive/transmit
some digital inputs/outputs (hard-wired signals)
from/to common control panel.
The list of such signals consist of following:
- Remote STOP signal. (Input)
- Remote START signal. (Input)
- Remote LOADING signal. (Input)
- Main motor START command (One shot signal
output to MCC)
- Main motor STOP (Contact signal to MCC)
- Shut down signal (Output)
- Alarm signal (Output)
- Maintenance signal (Output)
- Remote mode signal (Output)
- Loading signal (Output)
- Running signal (Output)
- Main motor running signal (Input from MCC)
- Main motor starter failure (Input from MCC)
- Main motor current (Analogue input, CT sec.: 0- 5
Amp. From MCC)
temperature scanner

A temperature scanner is provided for each


compressor for winding & bearing temperature
indication & control.
 A soft link from each scanner will be connected
serially to PLC in this Common Panel.
The tripping will be initiated for each compressor for
winding & bearing temperature through PLC & the
output for Trip will be activated in association with
trip command from each compressor.