5.air-Cooled Modular Chiller Selection
5.air-Cooled Modular Chiller Selection
Selection
System Design
Selection
Air-cooled Modular
Product Line Up
Product Line Up
Selection
Air-cooled Modular Chillers
25/30/35kW 55/60/65kW
130kW 200/210kW
Product line Up
Selection
Fan Coil
Unit
Selection
•Sc
et
•L l
M
oe
o
ac
d st
dt
u ep
3
l st
cF ep
a 2
aC st
r ep
lU
1
c
C
uo
h
lr
i
a
l
tA
l
Selection
iH
Selection
1. Load
calculation
Design
parameters
For civil building, we should think about capacity more than air volume,
especially the visible capacity when we choose FCU or AHU.
The second step, we have to check if the air volume meet the quality demand
of the AC room.
For example:
A hotel, Q=500KW, consider the same using ratio of AC room,
(0.7-0.8)*500=350-400kW
Select modular chiller: 6 pcs 65KW
Selection
System design
Selection
System
sketch
Selection
System
sketch
it can be used to control air temp. according to load. If room temp. is lower than set
temp. in summer, the valve will be off
Selection
System
sketch
It can be used to remove the air in the pipe system. And usually it be installed on the
top point of close water system.
Selection
System
sketch
Check valve
It can be used to prevent the medium from flowing backwards. And usually it be
installed on the outlet pipe of pump
Selection
System
sketch
Y-shaped filter
It can be used to prevent the impurity from blocking the water pipes. And
usually it be installed on the inlet pipe of unit, such as chiller.
Selection
System
sketch
it can be used to protect the chiller, when it check the water flow rate is lower than
normal level, it will get the chiller stop work. And usually it be installed on the outlet
Selection
System
sketch
Expansion tank
Expansion tank
It can be used to avoid the volume changing because water expands with heat
and contracts with cold. And usually it’s location is 1-2m higher than the water
• Th
e
• the
lay
sele
out
ctio
of
n
st
chil ep
of
led
aux
wat 4
ilia
er st
ry
pip ep
epar
• ts
Th
an
3
e
d st
• lay
con
Th ep
out
eden
of
2
sat
lay
echil
out st
ler
wat
of ep
er
FC 1
pip
U
eor
AH
U Selection
Selection
Step 1 The layout of FCU or AHU
FCU or AHU
Selection
Step 1 The layout of FCU or AHU
Typical
installation
Selection
Step 1 The layout of FCU or AHU
Typical
installation
Selection
Step 2 The layout of chiller
Air outlet Air outlet Air outlet Air outlet
>600
Air inlet
Compressor
Compressor
PC box
PC box
Water outlet
Flange
12# 14#
1#
850
2492
1514
850 × N+ 600 × (N- 1)
The modular chiller do not need special machine room, it can be installed in anyplace
where ventilation is fine.
Selection
Step 2 The layout of chiller
Module unit can be combined by single unit, double units or both. By connecting each
own inlet & outlet pipeline in series, 1-16 pcs module can be combined and the max
cooling capacity is 1040KW, unit system of principle is shown as follows:
30kw module
65kw module 65kw module
Direct Return
1
2 Reverse Return
Selection
Step 3 The layout of chilled water pipe and condensate water pipe
1. The diameter of the pipe which is connected to the FCU or AHU should be the
same as the relevant unit’s.
2. Formula :
D=√ 4000Q/3.14V
Q(L/s) : water volume
D(mm) : inner diameter of water pipe
V(m/s) : assumed velocity of water
Selection
Step 3 The layout of chilled water pipe and condensate water pipe
diameter(mm) 15 20 25 32 40 50
Close water system 0.4 ~ 0.5 0.5 ~ 0.6 0.6 ~ 0.7 0.7 ~ 0.9 0.8 ~ 1.0 0.9 ~ 1.2
Open water system 0.3 ~ 0.4 0.4 ~ 0.5 0.5 ~ 0.6 0.6 ~ 0.8 0.7 ~ 0.9 0.8 ~ 1.0
diameter(mm) 65 80 100 125 150 200
Close water system 1.1 ~ 1.4 1.2 ~ 1.6 1.3 ~ 1.8 1.5 ~ 2.0 1.6 ~ 2.2 1.8 ~ 2.5
Open water system 0.9 ~ 1.2 1.1 ~ 1.4 1.2 ~ 1.6 1.4 ~ 1.8 1.5 ~ 2.0 1.6 ~ 2.3
diameter(mm) 250 300 350 400 450 500
Close water system 1.8 ~ 2.6 1.9 ~ 2.9 2.0 ~ 2.8 2.0 ~ 2.8 2.1 ~ 2.8 2.1 ~ 2.8
Open water system 1.7 ~ 2.4 1.7 ~ 2.4 1.6 ~ 2.1 1.8 ~ 2.5 1.9 ~ 2.5 1.9 ~ 2.5
Selection
Step 3 The layout of chilled water pipe and condensate water pipe
MGB-D65W/SN2
MGB-D65W/SN2
Item A B C D E F G M
Water volume(m3/h) 2.23 3.46 5.36 6.9 2.23 4.14 5.69 12.6
Pipe diameter(mm) DN20 DN32 DN40 DN50 DN20 DN40 DN40 DN65
V(m/s) 1.97 1.2 1.19 0.98 1.97 0.92 1.26 1.06
Amendatory D DN32 DN40 DN50 DN50 DN32 DN40 DN40 DN65
Amendatory V 0.77 0.77 0.76 0.98 0.77 0.92 1.26 1.06
Selection
Step 3 The layout of chilled water pipe and condensate water pipe
MGB-D65W/SN2