Professional Documents
Culture Documents
Cleaver Brooks Training
Cleaver Brooks Training
▶ System Features
▶ Burner Control controls burner start and shutdown sequencing and
flame
and interlock monitoring
▶ Compatible with CB780E and CB120E Buner Controls and flame
scanner.
▶ Boiler Control monitors and displays connected boiler
parameters (operating pressure or temperature, stack
temperature, shell water temperature, O2% etc.)
▶ 6” color touch/keypad Human Machine Interface (HMI)
▶ Optimized boiler firing rate control
▶ Alarm/Fault indication and history – first out annunciation with time
stamp and displayed in order of fault occurrence.
▶ Thermal Shock Protection (includes warm-up routine, low fire hold &
hot- standby operation)
▶ CONTINUED
▶ O2 Monitoring and O2 trim
▶ Remote Modulation by Communications (EtherNet)
▶ Remote Set point by Communications (EtherNet)
▶ Boiler efficiency calculation
▶ Assured low fire cut off
▶ High stack temperature alarm and shutdown
▶ Ethernet communications
▶ Three firing modes: Single-point, parallel, or LOW-HIGH-LOW on fuel 2
▶ Supports control of a flue gas recirculation (FGR) damper
BURNER MANAGEMENT
Stack Transmitter –
Measures the stack
temperature. It gives 4- 20ma
output for measurement,
alarm and high stack
temperature shutdown. It uses
a thermocouple sensor.
Ambient Air transmitter–
Measures the ambient air
temperature that came from air
hood. It gives 4- 20ma output for
measurement.
Pressure Transmitter – Measures
the steam pressure. It gives 4-20ma
output for modulation of the firing
rate according to a desired
setpoint. It uses capacitance as the
variable for pressure measurement.
Water temperature
thermocouple –
Measures the water
temperature by means of
surface magnetic
thermocouple.
Surface
Signal Magnetic
Converter Thermocouple
Variable Frequency Drive –
Controls the speed of the
blower motor. It uses 4-20 mA
command and feedback.
When system
configuration and
calibration of actuators
are not configured.
When configuration
are done correctly
this is the main menu
screen
USER ID
NEX
T
NEX
T
NEX
T
NEX
T
NEX
T
NEX
T
NEX
T
A confirmation
button will
appear to
save the new
configuration.
Pressing main
will back you
to the main
screen
ACTUATOR CALIBRATION
Press
NEX Commission
T Actuator
NEX
T
NEX
T
NEX
T
Repeat procedure
from air actuator
Fuel 2 Actuator 1 commissioning.
NEX Pressing main will
must be T
commissioned. back you to the
(Fuel 2 = Main main screen
fuel)
SET COMBUSTION
▶ You can adjust the cut in/cut out of the boiler, Setpoint of the
boiler and hot standby temperature in this panel.
SETPOINT SETTING
Operating Pressure Control (OPC)
- The pressure control should be set slightly above the highest desired
steam pressure, but at least 10% lower than the setting of the safety
valves.
Burner Does Not start • Water level below • Refill water at proper
“Boiler Limits Open” required level. level
• HLC or OLC are open • Reset HLC
circuit
• ODS, LOPS, and • Check safety control
ALWCO are open and interlocks
circuit.
Burner starts but shutdown • Interlocks open circuit such • Check safety controls and
after a few seconds as AAPS, CAPS, LOPR, interlocks
“Burner Control alarm” “Lock and BMSI • Jumper device for testing. If
out Interlock” burner runs, replace
defective components.
COMMON FAULTS
Common Faults Possible Causes Action/Remedies
Main flame fail to ignite • Loose stoppage of fuel • Check safety controls and
supply interlocks
“Burner Control Alarm” • FD weak or defective • Jumper device for testing. If
“Main Flame Fail” • Lens dirty or sight tube burner runs, replace
obstruction defective components.
• Improper air-fuel ratio
(Lean Fire)
COMMON FAULTS
Common Faults Possible Causes Action/Remedies
Boiler detects low • Lack of water supply • Refill water and check
water. • Obstruction on water level on sight glass
feedwater line • Check feedwater
“Low water” • Inoperative Pump pipelines
Control • Check MC donnel
• Feedwater Pump not • Check feedwater
running pump and its controls
•THANK YOU!!!