Professional Documents
Culture Documents
POWER SYSTEMS -2 ELECTRICAL ENGINEERING
POWER SYSTEMS -2 ELECTRICAL ENGINEERING
V SEMESTER
EEC-303
Reference Books:
[R1] J. J. Grainger & W.D. Stevenson, “Power System Analysis” TMH Publication,
2003
[R2] Paul M. Anderson “Power System Protection” IEEE Press.
[R3] C L Wadhwa, “Electrical Power System” Wiley Eastern Ltd., 3rd edition 2000
[R4] D.P. Kothari and I.J. Nagrath “Modern Power System Analysis “ TMH 4th
Edition
1. The power consumption in case of static relays is usually much lower than that in case of
their electromechanical equivalents.
2. Hence burden on the instrument transformers (CTs and PTs) is reduced and their accuracy
is increased, possibility of use of air-gaped CTs is there, problems arising out of CT
saturation are eliminated, and there is an overall reduction in the cost of CTs and PTs.
3. Quick response, long life, shock proof, fewer problems of maintenance, high reliability
and a high degree of accuracy.
4. Absence of moving contacts and associated problems of arcing, contact bounce, erosion,
replacement of contacts etc.
5. Quick reset action—a high reset value and absence of overshoot can be easily achieved
because of the absence of mechanical inertia and thermal storage.
6. There is no effect of gravity on operation of static relays and, therefore, they can be
installed in vessels, aircrafts etc.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
51
Subject: PS-II, Instructor: Dr. Kusum Tharani
Advantages of Static Relays
9. The basic building blocks of semiconductor circuitry permit a greater degree of sophistication
in the shaping of operating characteristics, enabling the practical realization of relays with
threshold characteristics more closely approaching the ideal requirements.
10. By combining various functional circuits, several conventional relays can be substituted by
a single static relay. For example a single static relay can provide overcurrent, under-voltage,
single phasing, short-circuit protection in an ac motor by incorporating respective functional
blocks.
11. Static relays are very compact. A single static relay can perform several functions.
12. The characteristics of static relays are accurate and superior. They can be altered within
certain range as per protection needs.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
52
Subject: PS-II, Instructor: Dr. Kusum Tharani
Limitations of Static Relays
6.The static relays have low short-time overload capacity compared with electromagnetic relays.
7. Static relays are costlier, for simple and single function, than their equivalent electromechanical
counterparts. But for multi-function protection, static relays prove economical.
8.The production technology of plug-in-type static relays on the panel permits the manufacturing
of standard relays in mass and the customer’s needs can be met quickly by incorporating
required relay units on the panel. Static relays with ICs are cheaper than those with discrete
components.
9. Static relay characteristic is likely to be affected by the operation of the output device but this is
not so in case of electromagnetic relay because its operation is based on the comparison
between operating torques/forces.
11. Static relays are not very robust in construction and easily affected by surrounding
interference.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
54
Subject: PS-II, Instructor: Dr. Kusum Tharani
Need for Comparators
The application of a particular relay is governed by its characteristics and other
factors such as accuracy, operating time, reliability, burden, method of setting
adjustment etc.
The function of a protective relay is to sense any abnormal condition in the
system and send a signal to the breaker which in turn isolates the faulty section
of the feeder from the healthy one.
The relay does all this by comparing two quantities either in amplitude or in
phase.
The amplitude or phase relation depends on the conditions of the system and for
a predetermined value of this relation, indicative of a particular type and location
of fault, the relay operates.
Except in relays, such as overcurrent relays, where only one electrical quantity
overcomes a mechanical quantity such as the restraint from a spring, usually two
electrical quantities are compared.
The device that makes such comparison is called the comparator and forms the
heart of a protective of any relay is governed by the comparator.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
55
Subject: PS-II, Instructor: Dr. Kusum Tharani
General Equation for Comparators
It is observed that the requirement |S1 + S2| < |S1 – S2|
puts a condition on the phase relation between S1 and
S2 i.e. unless the phase difference between original
phasors S1 and S2 exceeds 90°, |S1 + S2| cannot be less
than |S1 – S2|.
So the original amplitude comparator with inputs now |
S1 + S2| and |S1 – S2| is a phase comparator i.e., a
converted phase comparator.
It is to be noted that the phase comparator in case of
static circuits is a cosine comparator as opposed to a sine
comparator in case
Department of Electrical of electromechanical
and Electronics relays
Engineering, BVCOE, New Delhi
67
Subject: PS-II, Instructor: KUSUM THARANI
Amplitude comparator
Amplitude comparator compares the amplitudes of two (or more) input quantities.
The phase angle between the quantities under comparison (inputs) is not
recognized or noticed by the amplitude comparator.
If the two input signals are S 1
and S2 (say S1 the operating and S2 restraining), the amplitude comparator gives
positive output only if –
S2/S1 < K.
The function is represented by a circle in the complex plane with its centre at the
origin. This defines the boundary of the marginal operation.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
68
Subject: PS-II, Instructor: KUSUM THARANI
Static Amplitude Comparator
The main purpose of a numerical relay is to protect the electrical network from
unexpected fault currents. Numerical relays are mostly preferred because of their versatile
characteristics.
A single Numerical relay can monitor multiple parameters like current, voltage,
Frequency, onset time, offset time, etc.
And the same relay can be used for analyzing and monitoring multiple faults such as over
current, over fluxing, different current and more.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
78
Subject: PS-II, Instructor: Dr. Kusum Tharani
Block Diagram for
Microprocessor based Relay
Output Module
The output module is the digital contacts that are actuated when a
trip command is given by the CPU.
These digital contacts are pulses that are generated as a response
signal. The response time can be changed according to the
application of the relay.
These classifications are made on the basis of logical operation of the relay
Over Current/ Earth Fault: When excessive current flows through a system
it will trip the circuit breaker. Used for transformer and feeder protection.
Directional overcurrent: It is operated when the fault drives the power to
flow in a particular direction (Opposite to the specified direction). Used in the
protection of Bus bar, Generator, and Transformers.
Differential: The differential relay is set to trip when the phase difference of
two or more identical electrical quantities exceeds the specified value. It can
Protect Transformers and Generators from localized faults.
Under/ Over Voltage: The voltage in an electric network might drop or rise
below or above a fixed value, the circuit is tripped under such conditions.
Distance: This type of relay is operated based on the distance between the
impedance of the fault and the position of the relay. They are mostly used in
the protection of transmission lines.
Current relays
Voltage relays
Frequency relays
Power relays Etc.
Technology Standard 1st generation relays. 2nd generation relays. Present generation relays.
Operating Principle They use principle of In this relays transistors and IC’s They use microprocessor. Within
electromagnetic principle. been used built software with predefined
values
Measuring elements/ Hardware Induction disc, electromagnets, R, L, C, transistors, analogue ICs Microprocessors, digital ICs, digital
induction cup, balance beam comparators signal processors
Measuring method Electrical qtys converted Level detects,comparison A/D conversion, numerical
intomechanical force, torque withreference value in analogue algorithm techniques
comparator
Surrounding Environment Depend upon gravitation and the Their value may vary with respect Remain Stable
value changes to the surrounding to temperature also.
magnetic fields also.
Relay Size Bulky Small Compact
Tap-Changing:
Transformer transformation ratio is changed whenever the
taps are changed.
Due to this CT ratios do not match with the new-tap
settings and result in flow of current in pilot wires even
during healthy condition.
However, this problem is also overcome by employing
biased- differential relay.
The relay coils are connected in star, the neutral point being
connected to the current-trans-former common neutral and
the outer ends one to each of the other three pilots. In order
that burden on each current transformer is the same, the
relays are connected across equipotential points of the three
pilot wires and these equipotential points would naturally be
located at the middle of the pilot wires.
The relays are generally of electromagnetic type and are
arranged for instantaneous action since fault should be
cleared as quickly as possible.
In this method, alternating current is injected into the field winding circuit
and ground along with a sensitive overvoltage relay and a current limiting
capacitor.
A single earth fault in the rotor will complete the circuit comprises the
alternating current source, sensitive relay and earth fault. Thus, the earth
fault is sensed by the relay.
The major disadvantage of such type of system is the leakage current that
flows through the capacitor.
This current unbalanced the magnetic field and increase the stress on the
magnetic bearing.
Another disadvantage of alternating current is that the relay cannot pick up
the current that normally flow through the capacitance to the ground.
Thus, care must be taken to avoid resonance between the capacitance and
the relay inductance.
Department of Electrical and Electronics Engineering, BVCOE, New Delhi
153
Subject: PS-II, Instructor: Dr. Kusum Tharani
AC and DC Injection Methods for Rotor Earth
Fault Protection
Where
Io = Maximum operating current in the primary of C.T.
If relay setting used is 15% then Io is 15% of full load
current of the largest machine and so on.
Greater percentage of windings of small capacity
machines running parallel get protected
(ii)Harmonic restraint: This is the most extensively used methods for making
the relays immune to harmonics caused by inrush. The restraint coils is
energized by the dc equivalent of bias winding current as well as the
harmonics.
Harmonic restraint circuit is formed by tuning XCXL which would permit
only currents of only fundamental frequency to enter the operating circuit
while the dc and higher harmonics are diverted onto the restraining
winding.
But this circuit may prove to be failure if the internal faults are also rich in
harmonics which may be caused due to an arc or if the CT saturates and
produce harmonics.
For this purpose an instantaneous over current relay is provided in the
differential circuit which is set above the maximum inrush current but will
operate in less than one cycle on internal faults. The circuit for the same
can Department
be given ofasElectrical and Electronics Engineering, BVCOE, New Delhi
199 Subject: PS-II, Instructor: Dr. Kusum Tharani
Harmonic Restraint Relay