Professional Documents
Culture Documents
CONTROLS VER 1
CONTROLS VER 1
• Introduction
• Control Actions
• Control Actions Analysis
• Control and Controlled Devices
• Types of Control Systems
• DDC Control Theory
• Control Points Classifications
• Points List
• DDC Design for HVAC Equipment
• Summary
2
Objectives
• Differentiate between controls and control
actions, and open and closed-loop control
• Recognize the three major control systems
• Identify the major components of DDC
• Define control points and create a Points List
• Build a DDC system that performs the
desired sequences of operation
Direct Digital Control (DDC): a type of
control where controlled and monitored
analog or binary data (e.g., temperature,
contact closures) are converted to digital
format for manipulation and calculations
by a digital computer or micro processor,
then converted back to analog or binary
form to control physical devices.
5
Energy Management System (EMS): a
system of computer applications used by
building engineering staff to monitor,
control, and optimize the building's
operating performance (e.g., energy
consumption, occupant comfort levels). EMS
optimizes building operating performance
through supervisory control programs that
utilize core BMS functionality.
6
Building Automation System (BAS): an
energy management system, usually with
additional capabilities, relating to the
overall operation of the building in which it
is installed, such as equipment monitoring,
protection of equipment against power
failure, and building security.
7
Building Management System (BMS): an energy
management system relating to the overall
operation of the building in which it is installed.
It often has additional capabilities, such as
equipment monitoring, protection of equipment
against power failure, and building security. It
may also be a direct digital control (DDC) system
where the mode of control uses digital outputs
to control processes or elements directly.
8
Sensor: device or instrument designed to
detect and measure a variable e.g
occupant sensor, temperature sensor
Controller: device that interprets the
sensor data and actuate a controlled
device or initiate a control sequence.
Controlled device: device that changes
based on the controller output
9
Throttling Range: change in the
measured variable (e.g. temperature) that
causes the controlled device to travel
from one end of its stroke to the other.
10
Throttling Range
11
Control Defined
15
• Input: Signal that goes to a DDC
controller (panel)
• Output: Signal that comes out of the
DDC controller (panel)
• Inputs and Outputs can be analog or
digital
07/15/24 16
• Digital Input – input signal to a DDC
controller that has two discrete states
such as on/off or yes/no
Fan status signal (on or off)
Filter dirty (yes of no)
Alarm from chiller (yes or no)
07/15/24 17
• Analog Input – input signal to a DDC
controller that has any value between a
minimum and a maximum
Room temperature sensor
Duct static pressure sensor
Return air humidity sensor
Room carbon dioxide sensor
Filter differential pressure sensor
07/15/24 18
• Analog Input – signal depends on the
type of sensor used
AI for voltage is 0-10 VDC
AI for amperage is 4-20 mA
AI for resistance is 0-135 ohm
07/15/24 19
• Digital Output – output signal from a
DDC controller to a component that has
two discrete states such as open/close
or turn on/turn off
Turn fan on
Close return air damper
Turn on lights
Dial a telephone number
07/15/24 20
• Analog Output – output signal from a
DDC controller to a control component
that has any value between a minimum
and a maximum
Modulate outdoor air damper
Modulate chilled water valve
Modulate pump speed (VFD)
07/15/24 21
• Analog Output – signal depends on the
type of device that is controlled
AI for voltage is 0-10 VDC
AI for amperage is 4-20 mA
AI for resistance is 0-135 ohm
07/15/24 22
• 0-10 V Pros
Low cost
Easy to troubleshoot
Nearly all controllers accepts 0-10 V signal
• 0-10 V cons
Signal strength decreases over long runs
Susceptible to electrical interference
07/15/24
• 4- 20 mA Pros
Low susceptibility to electrical interference
Low signal loss over long runs
Most controllers accepts 4-20 mA signal
Inherent condition detection
• 4-20mA Cons
High cost
07/15/24
Lower energy cost Lower operations
cost
07/15/24 25
• Why use BEMS?
– Growing complexity of building systems
– Demand for more efficient building operation
– Need to save energy & operating costs
– Need to increase flexibility & reliability
– Improve indoor environment & productivity
• Connect EMS to major building equipment to
– Control air conditioning & lighting to save energy
– Monitor all equipment to improve efficiency of
operations personnel & minimize equipment down
time
07/15/24 26
“Controls” Differentiation
• Controls (Noun)
the instruments, devices, and software that
sense conditions and cause actions to happen
the eyes, ears and mouth of the control system
• Controls (Verb)
the action plan of using controls to provide
desired results through a control sequence of
operation.
Controls
Graphic Symbol Graphic Symbol
Heating
Solenoid Valve
Thermostat
Cooling
07/15/24 29
C15960.009 FLOW SWITCH.dwg
07/15/24 30
Control
Cooling
Valve
Supply
Fan
Controller
Sensor
Control Levels
Building
Control
Exhaust Fan
Cooling Valve
Cooling Coil
Equipment
Control
Zone
Control
Open-Loop
Cooling
Valve
Supply
Fan
Controller
Manual Switch
ON
Open-Loop Control (Manual Switch)
- If the person in this room is too hot, they OFF
have to get up and turn on the equipment
- There is no feedback to turn the equipment
on or off
Open-Loop
Outdoor-air
Sensor
Airflow
Controller
Chilled
Water
Valve
Closed-Loop
Cooling
Valve
Supply
Fan
Controller
Sensor
Discharge air
Temperature sensor
Airflow
Controller
Chilled
Water
Valve
Control Reset (Closed/Open Loops)
Discharge Air
Outdoor Air Temperature Sensor
Temperature
Sensor
Airflow
Controller
Valve
Chilled
Water
Control Actions
07/15/24 44
Control Action
ON
(Opened)
OFF
(Closed) T1 T2 T3 T4 T5
07/15/24 46
Floating Control (Modulating)
07/15/24 47
Floating
07/15/24 49
Proportional (P)
07/15/24 50
Proportional (P)
07/15/24 51
Proportional (P)
07/15/24 52
Proportional (P) - Throttling Range
07/15/24 53
Control Action
Proportional (P)
Overshoot
Offset
Set Point
Controlled Variable
Undershoot
Measured
Value
Time
Controlled
Device
Position
Proportional Algorithm
Using the measured values of 70°, 71°, 72°, and 74° F with a 70° F set point.
The gain Kp = -20
The start value = 0
07/15/24 56
Proportional + Integral (PI)
07/15/24 57
Proportional + Integral (PI)
07/15/24 58
Control Action
Proportional + Integral (PI)
Overshoot
Measured Value
Set Point
Controlled Variable
Undershoot
Time
Controlled
Device
Position
Proportional and Integral Algorithm
Using a constant measured value of 72° F with a 70° F degree set point.
The gains Kp = -20 and Ki = 1
The start value = 0
Where the measured value creates an output based on:
Pterm = (set point – measured value) Kp, and
Iterm = (set point – measured value) Ki + Iterm (last)
07/15/24 61
Proportional + Integral + Derivative (PID)
07/15/24 62
Control Action
Set Point
Controlled Variable
• Proportional term
–Proportional to error
• Integral term
–Changes with time even with constant error
• Derivative term
–Changes with change in error
Time
Proportional Algorithm
Using the measured values of 70°, 71°, 72°, and 74° F with a 70° F set point.
The gain Kp = -20
The start value = 0
Control Deals
Control Concepts Added Benefit Response to Disturbance
Action with
P
Control signal
Proportional Signal proportional OFFSET
Error proportional to
(P) to error
error (demand based)
P+I
Integrates error
Integral Eliminates offset
Time over time to respond
(I) over time (accuracy) UNDERSHOOT
to small error
P+I+D
Shortens settling time
Responds to rate
Derivative (quick response) and OVERSHOOT
at which set point
(D) Rate lessens overshoot/
is approached
undershoot
(precise)
Overshoot/Undershoot/Settling
Time
Measured Value Overshoot
Set Point
Controlled Variable
Undershoot
Time
Settling
Time
Offset
Measured Value
Set Point
Offset
Controlled Variable
Time
Common HVAC Control Strategies
Application Strategy Action or Algorithm
Mixed Air Dampers PI
Chilled Water Coil Valve with
Discharge Sensor PI
Flow Tracking
Control of Return Air PI
Temperature Control P
P = Proportional
PI = Proportional + Integral
PID = Proportional + Integral + Derivative
Control and Controlled Devices
Actuator
Control Thermostat
System-level
Control
Unit-level Control
07/15/24 81
• Stand-alone control
• Safeties, alarms and diagnostics
07/15/24 82
The BAC–5801 and BAC-5802 are native BACnet, fully
programmable controllers designed for general purpose applications.
Use these versatile controllers in stand-alone environments or
networked to other BACnet devices. As part of a complete facilities
management system, the BAC–5801 and BAC-5802 provide precise
monitoring and control of connected points.
07/15/24 83
The BAC-7302 and BAC-7302C are native BACnet, fully
programmable, controllers designed for roof top unit
applications. Use these versatile controllers in stand-alone
environments or networked to other BACnet devices. As part of
a complete facilities management system, the BAC-7302 and
7302C controllers provide precise monitoring and control of
connected points. 84
The BAC-7000 series VAV controllers are BACnet
Advanced Application Controllers designed for VAV
terminal units. An integrated actuator and the supplied
programs make these ideal controllers for single duct
pressure independent or pressure dependent VAV
terminal units.
07/15/24 85
The BAC-7303 and BAC-7303C are a native BACnet, fully
programmable controllers designed for fan coil units. Use
these versatile controllers in stand-alone environments or
networked to other BACnet devices. As part of a complete
facilities management system, the BAC-7303 controllers
provides precise monitoring and control of connected
points.
86
The KMC Controls Full BAC BAC–5050 is a multi-port BACnet router.
07/15/24 87
These native BACnet, fully programmable, direct digital
controllers are factory pre-programmed and pre-
configured for use in Under Floor Air Distribution
(UFAD) applications.
88
The KMC FlexStat is a (B-AAC) BACnet advanced application
controller and sensor in a single, attractive package that creates
a flexible solution to stand-alone control challenges or BACnet
network challenges in any size of commercial and industrial
buildings.
07/15/24 89
The BACnet Building Controller (B-BC) is a high-
performance, native BACnet direct digital controller. As
part of a complete interoperable building automation
system, this 16x16 B-BC provides precise monitoring and
control of connected points. Integrated into the controller
is a BACnet router, web server, and expandable I/O (CAN-
A168EIO expansion module) in a native BACnet device.
90
DDC Control System
Network Local
Schedules Fans
CO2
CPU Towers
Actuator
GENERAL
PURPOSE
DDC Cooling
Fans CONTROLLER Tower
Outside Air Fan Status
Temperature Switch
• Controllers
• Sensors
• Control Devices
• User Interfaces
Centralized DDC System
Polling
DDC Network Control Panel
Communication
Optional Panel
Distributed DDC System
Chiller
AHU
Peer-to-Peer
DDC Network
Communication
Fan Coil
General Purpose Controller
Sensors User Interface
Tower
uts
In p
{
Pump uts
utp
Actuator O
Transformer
24 Vol
Power
Input
t
{
Communication Wiring
DDC Network
User Interfaces
Equipment-Mounted
Hand-Held
Devices
Computer Software
Open-Loop Control
Resulting
No Feed Back Action
Closed-Loop Control
Resulting
Feed Back Action
HVAC PI Algorithm
HVAC Algorithm =
Specifically programmed control routine selected
and configured for the HVAC application
DDC Controller
Error = (set point – sensor)
Input Pterm = error KP Output
Sensor Iterm = error KI + (last Iterm) Device
Output = Pterm + Iterm
Resulting
Feed Back Action
Control Point Types
INTERFACES
Network Local
Relay
Temperature Algorithm Solenoid
AI DO
Libraries Relay
Static Pressure Damper
AI AO Control
CO2
CPU
Tower Fan
AI AO VFD
Inputs DDC Controller Outputs
• Binary Input (BI) or Digital Input (DI)
Example: Fan status (on/off)
• Binary Output (BO) or Digital Output (DO)
Example: Start/stop fan
• Analog Input (AI)
Example: Temperature
• Analog Output (AO)
Example: Control valve position
07/15/24 106
Typical I/O Channel Signals
AI DI
• 10,000 (@77 F) thermistor • Relay closure
• 5,000 (@77 F) thermistor • Can be pulsed
• 1,000 (@70 F) RTD
• 4-20 mA current
• 2-10 vdc voltage
AO DO
• 4-20 mA current • Relay closure
• 2-10 vdc voltage • 24V contact closure
Points List
DDC Design for HVAC
Equipment
Designing a DDC System
Damper
3. Mixed Air Dampers
Actuator
4. Fan Status
5. Time Scheduling
6. Set point Table
Set points:
•Occupied
– Cooling
75° F
– Heating
07/15/24 112
70° F
Step 2 – Desired Controlled Devices
DO DO
DX Cooling Electric Heating
07/15/24
Stage #2 Stage #2 113
Step 3 – Control Action Selection
REQUIRED ACTIONS
1. Turn fan on/off based on the
occupancy schedule
2. Stage DX cooling based on
supply and average space
Damper
Actuator
temperatures
3. Stage electric heating based
on the supply and average
space temperatures
4. Position mixed air dampers
based on the outside air and
MOST REQUIRED ACTIONS average space temperatures
CAN BE ACCOMPLISHED
USING TWO-POSITION CONTROL
07/15/24 114
Step 4 – Sequences of Operation
• Schedule multiple heating and Damper