Professional Documents
Culture Documents
dokumen.tips_mcm3320-application-training-switchgear-engineer-training-083006-rev4-new-cummins
dokumen.tips_mcm3320-application-training-switchgear-engineer-training-083006-rev4-new-cummins
QTQ Training
Documentation
PGA Controls Engineering:
1. Kevin Aufderhar
2. Paul Dahlen
3. Rich Scroggins
G1
GM UM
G2
G3
AUX101
G4 AUX102
Breakers
or
ATS
Feature Validation
AC Metering
3 Phase metering of genset bus and utility bus
simultaneously
Phase and Total/avg metering of V, A, kW, kVAR,
kVA, PF, Hz
Phase and total metering of +kWh, -kWh, +kVARh, -
kVARh, kVAh for each source
CT secondaries of 1A or 5A
PT accepts 0-480VLL directly; external PT for higher
voltages (up to 35000V)
PT and CT inputs pre-calibrated
Breaker Control
interface for both genset main and utility main
close and open control – momentary energization until
desired position is achieved
a/b and tripped breaker position inputs
adjustable breaker recharge time delay to prevent fail
to close due to inadequate charge time
Breaker Control
utility paralleling enable output
breaker inhibit control input
breaker diagnostics with appropriate system control
reaction
adjustable fail to close and fail to open time delays
paralleling fail to disconnect diagnostic with
configurable system control reaction
Breaker Control
anti-pump avoidance logic – external breaker position
contacts not required in series with trip coil
breaker inhibit output to control individual genset
paralleling breakers in applications with no gen main,
and for backup disconnect protection capability
System Topologies
Transfer Pair (UM / GM)
Common Bus (UM / no GM)
Isolated Bus (GM)
Isolated Bus (no GM)
Master Synchronizer Only
System Topologies
Transfer Pair (System Types 2,3,4,8,10,11)
G1 G2 G3 G4
MCM
3320
UM GM
Load
System Topologies
G1 G2 G3 G4
MCM
3320
UM
Load
System Topologies
G1 G2 G3 G4
MCM
3320
GM
Load
System Topologies
G1 G2 G3 G4
MCM
3320
Load
System Topologies
G1 G2 G3 G4
MCM
3320
Sync
Source Check
Multiple MCM3320s
(External)
master inhibit input will inhibit the synchronizer and
power transfer control functions
use in complex systems with multiple transfer pairs and
multiple MCM3320s
external logic device is required to assert the master
inhibit as required (e.g. during a retransfer sequence of
multiple pairs)
future enhancement will allow automatic priority control
through interconnected MCM3320s (similar to First Start
Bus PT logic)
Extended Paralleling
MANY options available for controlling kW and kVAR in
extended paralleling mode (kVAR not applicable for
PCC3100)
kW and kVAR can be independently controlled in any
combination of base load (control the power @ gen bus)
or peak shave (control the power @ utility bus)
load control operates independently of the number of
gensets that are online
Maximum of 20 gensets
kW base load control selectable as open loop or closed
loop
kW peak shave control is closed loop only
Extended Paralleling
setpoints can be set from InPower, HMI, Modbus, or via analog
hardware 0-5V inputs
extended parallel start input starts/stops the mode
soft load ramping
separate diagnostic for kW and kVAR if unable to acheive
setpoint within 60 seconds
System Scheduler
Load Demand
Load Add/Shed
Modbus RTU
intended for PLC interface
published register map
read/write access
operational data, control, and setup variables
MCM3320 is Modbus slave
RS232 or RS485 connection
settable address (allowing multiple MCM3320 slaves on RS485)
communications setup and diagnostics
Diagnostics
individual On-Board LEDs for:
Utility Available
Utility Connected
Genset Available
Genset Connected
Not In Automatic
Common Warning
Heartbeat
Synchronizing
Synchronized
Fail To Sync
Modbus Communication Activity
Diagnostics
LED Indicators
Utility Genset
Connected Connected
Fail to Sync
Not In Common Heartbeat
Blink = Sync Automatic Alarm (blink)
Solid = Ok
to Close
Diagnostics
On-Board seven segment LED for indication of:
System State indication of what the control is currently doing
Fault Code Readout (hold fault reset switch active for >5sec to change to
fault code readout mode)
Diagnostics
42 diagnostics (warnings and events)
each event or warning is mappable to 8 customer low side
driver outputs
active warning codes can be read out on 7segment LED on
board
some warnings alter control operation
warnings are latched until user fault reset
events are not latched
InPower V5.5
Flexible Topology
Annunciator Support
Annunciator 1 Layout Annunciator 2 Layout
Test
Extended Parallel
Gen Bus Overload
Load Demand
Part Numbers
MCM3320
Genset CT Inputs Utility CT Inputs Utility PT Input
(1A or 5A) (1A or 5A) (480V LL Max)
TB7
Genset PT Input
TB6
(480V LL Max)
TB2
Switch IO /
DC Power In
Analog IO TB9
J14
Modbus RTU TB8 InPower or
TB15 Modbus RTU
(RS232) TB1 J17
(RS485)
TB3 TB10
Hardwired IO
B+ Input1 Master Freq Bias
B+ Input2 Master Volt Bias
B+ POWER BIDIRECTIONAL
Gnd Master Inhibit
Gnd
RELAY OUTPUTS Start Gensets Relay
CAN (Master)
RS485 PCCNet COMMUNICATIONS
RS485/232 Mon/MB
Load Govern Enable
Load Demand Gen1
Extended Para Start Load Demand Gen2
Sync Enable DISCRETE Load Demand Gen3
OUTPUTS Load Demand Gen4
Utility Source Failure (low side drivers)
DISCRETE Cfg Out1 (com warn)
INPUTS
Transfer Inhibit (active low w/ Cfg Out2 (fail to sync)
Retransfer Inhibit pullup) Cfg Out3 (gen avail)
Gen CB Tripped Cfg Out4 (util avail)
Util CB Tripped Cfg Out5 (fail to discon)
Gen CB Inhibit Cfg Out6 (sync’d)
Util CB Inhibit MCM3320 Hardware I/O Cfg Out7
Manual Cfg Out8
Paralleling Gensets
Test Start Breaker Inhibit
Fault Ack/Reset
Gen1 Available
Gen2 Available Relay Supply
B+ OUTPUTS
Gen3 Available
Gen4 Available
Override
ANALOG
OUTPUTS
kW Load Setpoint BREAKER kW Master Load Control
ANALOG
kVAR Load Setpoint INPUTS INTERFACE
(discrete inputs / kVAR Master Load Control
(0-5V)
relay outputs)
GEN BUS/UTIL
V/I V/I
Gen Position B
Gen PositionA
Util Position B
Util PositionA
Gen Close
Gen Open
Util Close
Util Open
Gen Utility
P. Dahlen
9/8/05 Load
B+ Power
PT Inputs
CT Inputs
HW Discrete Inputs
HW Discrete Inputs
HW Discrete Outputs
HW Discrete Outputs
HW Bidirectional Discrete
HW Analog Inputs
HW Analog Outputs
HW Bidirectional Analog
Communications
Communications
Port2:
– Protocol Options
• Modbus RTU (MCM3320 is SLAVE)
• Mon (Service Port for InPower/Setup Tools)
• Controller automatically detects protocol
– Physical
• RS232 on J14 (DB9 pins); Null Modem cable
• RS485 2-wire on TB15
• RS485 is default; control switches to RS232 when
RS232 RTS to CTS pins are jumpered by cable
HMI112 Bargraph
AUX101/2 IO Module
Connect to Grounded
Chassis
Relay LEDs
ON = Energized Relay LEDs
ON = Energized
P1 (PCCNet, Wakeup)
P3 (Relays - NC) Aux102 Board Revision
Level: First letter on barcode
Green LED: PCCNet
(read from left to right) must
Communcations OK
P2 (Relays - Com) be “C” or higher letter.
Red LED: PCCNet P3 P4
Communcations Not (Relays) (Relays)
OK P2 (Relays) P1 (Relays - NO)
Connections
Application Configuration
Primary Settings:
System Topology
Transition Type
Extended Parallel Enable
Test With Load Enable
Settings are trims (can be saved) or can
be dynamically set via Modbus, InPower
or HMI
Application Configuration
Application Configuration
Transition Type
Open Transition (default)
Hard Closed Transition (<100msec overlap)
Soft Closed Transition
Extended Parallel Enable
Disabled (default)
Enabled
Test With Load Enable
Disabled (default)
Enabled
Application Configuration
System Information
System Information
System Information
System Setup1
System Setup2
HW SW
SW HW
(enabled)
<Output Signal Name> + " Override Cmd"
Output
HW Update Register <Output Signal Name>
<Input Signal Name>
(disabled)
AC Metering Setup
AC Metering - Voltage
AC Metering - Current
AC Metering - Power
AC Metering - Energy
AC Metering Setup
AC Metering Calibration
• MCM3320 is
factory
calibrated
• Voltage and
Current can
be adjusted in
the field if
needed
Breaker Control
Breaker Diagnostics:
Fail to Close (adjustable delay)
Fail to Open (adjustable delay)
Breaker Contacts
Breaker Tripped
Fail to Disconnect
Diagnostics results in warning and appropriate
control reaction
Breaker Setup
Sensors
Sensor - Undervoltage
SensorUnderVoltage
- Undervoltage
Sensor
Status
PICKED UP
(good)
DROPPED OUT
(bad)
Voltage, V
Dropout Pickup Nominal
Voltage Voltage System
Voltage
(100%)
Sensor - Overvoltage
Sensor - Overvoltage
OverVoltage
Sensor
Status
PICKED UP
(good)
DROPPED OUT
(bad)
Voltage, V
Sensor - Frequency
Sensor - Frequency
Frequency
Sensor
Status
PICKED UP
(good)
DROPPED OUT
(bad)
Frequency, Hz
Sensors - Misc
Operating Mode
PTC
NOT
ENABLED
T99
T0
UTILITY
CONNECTED
Open Close
Utility U1 U3 Genset
U2 U4
No
T1A Command T2A
Close
Utility Open
T3A Genset
N2 T2B P4
N1
NO P3
SOURCE No
No
CONNECTED Command PARALLELED
Command
N3 P1
Close N4
T1B T4A P2 Open
Genset
Utility
T4B No T3B
Command
G4 G2
Open G3 G1 Close
Genset Utility
GENSET
CONNECTED
Timers
Start Timer
Stop Timer
Timer in each PTC State:
– Programmed Transition Timer (No Source Connected)
– Transfer Timer (Utility Connected)
– Retransfer Timer (Genset Connected)
– Maximum Parallel Timer (Paralleled)
Override
Synchronizer On / Off
Synchronizer Control
Sync Check
Synchronizer Diagnostics
Synchronizer On / Off
Synchronizer Control
Synchronizer Control
Sync Check
Synchronizer Diagnostics
Sync Setup
Load Control
Load Control
Soft Loading
Extended Paralleling
kW Control
kVAR Control
Diagnostics
Performance / Tuning
Soft Loading
Extended Paralleling
kW Control Options
Genset Controllers
» MCM3320 does nothing
» ONLY OPTION WHICH WILL WORK ON PCC3100 GENSETS
Gen Bus % Level (open loop)
» MCM3320 puts out fixed %kVAR command
Gen Bus Power Factor (open loop)
» MCM3320 puts out %kVAR command based on power factor
setting and what is currently being put out on the %kW command
output
Gen Bus kVAR (closed loop)
» MCM3320 adjusts output command to get desired kVAR at gen
bus metering point
Gen Bus Power Factor (closed loop)
» MCM3320 adjusts output command to get desired power factor at
gen bus metering point
setpoint source
120 1.2
110 1.1
%kW/kVAR
100 1
PowerFactor
90 0.9
80 0.8
%kW / %kVAR
Power Factor
70 0.7
60 0.6
50 0.5
40 0.4
30 0.3
20 0.2
10 0.1
0 0
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 3.25 3.5 3.75 4 4.25 4.5 4.75 5
Scheduler
Scheduler
Extended Paralleling Clarification
To use Extended Paralleling with the Scheduler, the
Extended Parallel Enable must be set to Enabled
If program run mode = Extended Parallel, but Extended
Parallel Enable = Disabled, there will never be extended
paralleling (nothing will happen when program becomes
active)
Some applications do not allow extended paralleling, so
this provides one setting to disable all extended
paralleling
Scheduler
Test With / Without Load Clarification
Scheduler will follow the Program Run Mode setting
– If Program #1 Run Mode = With Load, system will run with load
– If Program #1 Run Mode = Without Load, system will run without
load
The setting of Test With Load Enable variable does NOT apply
to Scheduler
– E.G. If Test With Load Enable = Disabled, but Program #1 Run
Mode = With Load, program will run with load
Test With Load Enable only applies to Test Start switch input
(hardwired or Modbus or HMI)
This may be confusing because it is different than how the
Extended Parallel Enable is used by the MCM3320
Scheduler Setup
Program Overlapping
Program1
Program1 runs for its entire period
Program2
Program2 does NOT run
Exception Operation
Exceptions only block the START of a program; a program
started outside of the exception period will not be canceled by
an exception
Program1
Exception1
Program1 does NOT run
Program1
Program1 runs for its entire period
Exception1
Priorities
Utility Failure will supersede any scheduler program
An active program will resume when the utility source has become
available again
Two examples are shown below
Program1 (no load)
EXAMPLE#1:
Utility fails while gensets running no load
Utility Failed
due to Program1. System will transfer load
to gensets. When utility returns, system load
UM Closed Closed
will remain on gensets until Program1 ends.
Breaker Open (It does NOT retransfer until Program1 ends.)
Closed
GM Open Open
Breaker
Operating Sequences
Normal Sequences1
Utility Fail / Return
Extended Parallel
Test (with or without load)
Sequences are affected by
Transition Type
Operating priority
Faults2
1
Refer to MCM3320 Operating Sequences document for listing of normal sequences
2
Refer to MCM3320 Abnormal Conditions Operation document for description of control reaction for
fault conditions.
Operating Priorities
Load Demand
Fixed Sequence
• GenA = Gen2
• GenB = Gen1
• GenC = Gen4
• GenD = Gen3
Sequence can be changed any time – even when load demand
is operating
Must issue “Refresh Sequence” command after defining the new
sequence in order for it to take effect (HMI211 does this for
you).
On change, only the appropriate gensets will restart, then after
time delay, unnecessary gensets stop in sequence
Shutdown Decision
[Genset Bus Load < Shutdown Percent * (Total Online
Capacity – kW Rating of Next Genset to Shutdown)] = true
continously for Shutdown Delay
Restart Decision
Genset Bus Load > Restart Percent * (Total Online
Capacity)
Sequence has changed due to operator or run hours
Genset Bus is overloaded
Genset(s) have failed
Load Demand Enable changed to Disabled
MCM3320 has detected a problem with AC metering
4000
Gen4 Stop
3500
Gen4 Restart
ity
Online Capacity, kW
3000 ac
Cap
Gen3 Stop
oad=
2500
Gen3 Restart L
2000
4 Gensets each rated at 1000kW
Gen2 Stop Shutdown Percent = 60%
1500 Gen2 Restart
Restart Percent = 80%
GenA = Gen1
1000
GenB = Gen2
GenC = Gen3
500 GenD = Gen4
0
0 500 1000 1500 2000 2500 3000 3500 4000
Total Load, kW
Rev 1.5 prd
152
June 13, 2006
FUNCTIONS
Overload Operation
If Genset Bus Overload fault occurs, ALL load demand stopped
gensets will restart
Condition is latched until overload no longer exists and operator
resets the fault
Individual Genset Failure Operation
If a single genset fails, that genset is removed from the load
demand logic; fault occurs
If available, a stopped genset will restart to replace the failed
genset
When the failed genset comes back online, it will be readded to
load demand logic and normal operation will resume
Genset Bus Failure Operation
If the genset bus fails (goes “Not Available”), ALL load demand
stopped gensets will restart
Cable
Ribbon
MCM3320 AUX102 Input1 Input2 Input1 Input2
Load 5 Load 6
Add Shed Add Shed
PCCNet
Port
ATS CONTROL
Add and Shed Relays have FormC contacts
Add Relay energizes continuously to add the load; typically
used to tell ATS that it can transfer to genset
Shed Relay energizes continously to shed the load; typically
used to tell ATS to shed load (go to neutral position)
Use of pilot relays may not be required
ATS MONITOR
Two inputs available to monitor ATS
Input 1 for Source 1 switch position
Input 2 for Source 2 switch position
ATS Position monitor = No Source Connected, Source 1
Connected, Source 2 Connected
ATS monitoring is provided for operator benefit only;
connections are OPTIONAL; Load Add Shed function does
not use this information
Timed Add
After Last Genset
Is Online
Gen2 Gen1 Gen3
Online Online Online
TIME
Genset Genset
Bus Bus
Overload Overload
Condition = Condition =
ACTIVE INACTIVE
TIME
Shed Shed
Level 1 Level 2
ON ON
Load Load
Shed Shed
Delay Delay
TIME
Utility Bus Utility Bus Utility Bus Utility Bus Utility Bus
1/4 sec Load Add Load Add
Load Add Load Add Load Add
Delay Delay Delay Delay Delay
Modbus RTU
RS485 OR RS232
MCM3320 is Slave
Configurable Address, Baud, Parity
Register Map Published
Setup, Control, and Monitor of MCM3320s
Steve Prater has developed some Quantum /
Momentum PLC code
Modbus Modbus
Address
System Name Access
Specifications Description
0: Master Synchronize Only
1: Isolated Bus w/out GM Sets the system topology. THIS
2: Isolated Bus w/GM
42300 System Topology Read/Write
3: Common Bus RESETS OTHER APP CONFIG
4: Transfer Pair SETTINGS!
Default: Master Synchronize Only
0: Open Transition
1: Hard Closed Transition sets the type of transition that will be
42301 Transition Type Read/Write
2: Soft Closed Transition used
Default: Open Transition
0: Disabled
use to enable extended paralleling
42302 Extended Parallel Enable Read/Write 1: Enabled
operation
Default: Disabled
Modbus RTU
Diagnostic Tools:
• Message Counters
• Exception Counter
• CRC Counter
Available through InPower or by Modbus
Diagnostic Function (code 08)
Historical Data
Energy Accumulators
HMI 211
HMI112 Bargraph
HMI112 Setup
Simulator Overview
Simulate Operating Scenarios
– Utility Fail / Return Soft CT
– Synchronizer Performance Plotting
– Test With / Without Load
– Extended Paralleling
– Faults
MCM3320
switch
inputs
Breaker fault
simulation
MCM3320
switch inputs
Gen is available
when genset
breaker closes
Utility bus
control
Bus
voltage
Alternator
Load
Load
Engine
InPower DOWNLOAD
“Initial Calibration”
» All trim values will revert to default settings
» Any custom settings will be lost
» Historical data will be lost
» Factory calibration data will NOT be lost
» Field calibration of voltage / current will be lost
VARIABLES
VARIABLES
Application Flexibility
Participant Application Examples
Application Flexibility
Application Flexibility
Application Flexibility
Application Flexibility
Application Examples
Participant Examples ?
YES
G1 G2 GN
52-UM1
52-GM1
52-F1 ... 52-FN
G1 G2 GN
YES
52-UM1
NO
G1 G2 GN
52-UM1
52-GM1
52-F1 ... 52-FN
YES
G1 G2 GN
52-UM1
52-GM1
52-F1 ... 52-FN
G1 G2 GN
MAYBE
52-UM1
52-GM1
52-F1 .. . 52-FN
CT Shorting Block
Expansion
SID Board
(Load Add Shed Control and Status) (Load Add Shed
Control and Status)