Professional Documents
Culture Documents
Me 414 He Presentation
Me 414 He Presentation
Me 414 He Presentation
Project Goals
y Design Heat Exchanger
y Create a light weight heat exchanger y Heat exchange must be as efficient as possible y Cost must be kept low as possible y The size of the heat exchanger must be under design constraint
Project Guidelines
y During the process of a liquid chemical product, its temperature needs
water
y City water is available at 20 C y Mass flow rate is adjustable and one of the design parameters to be selected y Exit temperature of city water from the heat exchanger is a function of the selected mass
Project Optimization
y Must cool the chemical from 45 C to 25 C y Heat exchanger length can not exceed 7 meters y Heat exchanger shell diameter can not exceed 2 meters y Minimize heat exchanger shell and tube weight hence the cost y Minimize heat exchanger pressure drop
Professor Toksoy
Chemical to be cooled was set as Shell side liquid Mass flow rate of cooling water = 220 kg/sec Shell ID = .889 m Shell thickness = 5 mm Tube OD = 6.35 mm Tube thickness = .457 mm Tube Length = 2.88 m Baffle space = .6 m Helical Baffles Counter flow One shell pass and one tube pass Aluminum was used for both shell and tube materials Gnielinski equation used for tube side Nusselt correlation Square tube pitch
shell side pressure drop to a minimum we needed to keep the mass flow rate in the shell low. The only way we found of doing this and getting the desired Q was to push the chemical to be cooled through the shell. Mass flow rate of cooling water = 220 kg/sec - For these inputs this calculates out to an average tube side fluid velocity of ~1 m/s which falls within the recommended range of .9 2.4 m/s. Tube OD = 6.35 mm - The small OD was needed to increase the surface area for heat transfer for a given shell ID. Tube thickness = .457 mm - The small tube thickness was needed to increase the heat transfer coefficient and also reduced the total material weight and cost.
calculated Q. Baffle space = .6 m - Although slightly larger then the recommended value of 40-60% of shell ID, .6 m worked well. Helical Baffles A helical baffle will increase the heat transfer coefficient considerably without dramatically increasing pressure drop due to the nature of the flows. Counter flow - Because of the narrow band of temperatures between the two fluids, a counter flow arrangement was used in order to increase the log mean temperature difference between the two fluids without having to increase the mass flow rate of the water to very high levels.
tube because currently the program does not calculate pressure drop due to multiple passes correctly. We discovered this late into the project and did not have time to fix the issue. If the pressures were calculated properly the water output temperature for one shell pass and two tube passes must stay below 28.33 deg C in order to keep the log mean temperature difference correction factor valid for the given temperature requirements. Aluminum was used for both shell and tube materials - Aluminum was chosen for its excellent heat transfer properties and its reduced weight. Gnielinskis equation used for tube side Nusselt correlation For the calculated Reynolds number of 5800 this correlation is most applicable. Petuhkov Krillovs correlation is used for Reynolds number larger then 104.
Nusselt Correlation
D.O.E. Run 1
Main Effects Plot for q_Calc
Data Means
mdot Shell 1600000 1400000 1200000 1000000 Tube Length
Mean
800000 200 Shell 1600000 1400000 1200000 1000000 800000 0.5 1.5 240 2 4
Mean
1000 200 Shell 5000 4000 3000 2000 1000 0.5 1.5 240 2 4
Mean
Mean
240
D.O.E. Run 1
y Factors
y Shell mass flow rate y Tube length y Shell internal diameter
result of increased surface area. y Shell I.D. and tube length had the greatest affect on weight, the larger the shell the more tubes can fit inside. y Shell side pressure drop increases with tube length and mass flow rate. Dramatic decrease as shell ID increases. y The only factor affecting the tube side pressure drop was tube length.
D.O.E. Run 2
Main Effects Plot for q_Calc
Data Means
5600000 5400000 5200000 5000000 Baffles Space Tube Th 2500 2450 2400 2350 Baffles Space
Mean
0.8
0.000457
0.000711
Mean
4800000
2300 0.3 2500 2450 2400 2350 2300 Baffle Cut 0.8 0.000457 0.000711
0.5
0.1
0.5
Mean
Mean
2000 0.3 10000 8000 6000 4000 2000 0.1 0.5 Baffle Cut 0.8 0.000457 0.000711
12000 0.3 20000 18000 16000 14000 12000 0.1 0.5 Baffle Cut 0.8 0.000457 0.000711
D.O.E. Run 2
y Factors
y Baffle Space y Tube Thickness y Baffle Cut
y Baffle spacing has a large affect on q and shell side pressure drop. y Tube thickness was the only factor affect HE weight in this DOE. y Baffle cut doesnt seem to have any affect on other parameters. y We fixed baffle spacing because it heavily influenced shell side
pressure drop.
Final D.O.E.
Main Effects Plot for q_Calc
Data Means
Tube Length 8000000 7000000 6000000 5000000 Shell ID
Mean
Mean
4000000 2 8000000 7000000 6000000 5000000 4000000 0.00635 0.01270 Tube OD 4 0.889 1.500
Mean
Mean
0.889
1.500
0.889
1.500
0.01270
0.00635
0.01270
Final D.O.E.
y Final optimization factors
y y y y
Mass flow rate of the shell fluid fixed to 220 kg/s Tube length Shell internal diameter Tube outer diameter
y We adjusted the ranges of our chosen factors and ran the DOE
again. y The mass flow rate only affected the shell side pressure drop at this stage of the design. We chose the shell side mass flow rate based on what we decided would yield reasonable shell outlet temperature using counter flow.
affect on the heat rate. y Shell ID has the smallest relative affect on heat rate. y Shell ID had a negative affect on heat rate. y This was a result of more tubes decreasing the velocity in the tube. y The result is laminar flow inside the tube.
95 90 80
P ercent
70 60 50 40 30 20 10 5 B AB
300
400
drop. y Shell ID has no affect on tube pressure drop. y We expected tube OD to have a larger affect on tube side pressure drop.
Pareto Chart of the Effects
(response is DP_Tube, Alpha = 0.05)
F actor A B C Name Tube Length S hell ID Tube O D
Term
affect on shell side pressure drop. y The affect of tube OD on the pressure drop was surprising.
the 60 triangular pitch tube arrangement. y As tube OD grows larger there is more pressure drop in the shell.
Term
diameter the more tubes we could fit inside, thus increasing weight.
y Because tube length
determines the length of the heat exchanger, it too has a large affect on heat exchanger weight.
Term
2000 Effect
3000
4000
Design Optimization - 1
The design optimized to our original design. We expected our final tube diameter to be 6.35 mm with a mass flow rate of 220 kg/s. y Optimal Tube OD was 8.3mm The tube length was longer than our original design called for, which was a result of maximizing the q calculated. We set target values for the shell and tube side pressure drops. We set a target range for total weight between 900-1100 kg.
y y
y y
Design Optimization - 2
New High D Cur 1.0000 Low Composite Desirability 1.0000 Weight Minimum y = 2288.8141 d = 1.0000 DP_Shell Minimum y = 1805.0741 d = 1.0000 DP_Tube Minimum y = 5865.8838 d = 1.0000 q_Calc Maximum y = 5.454E+06 d = 1.0000
y
The design optimized to our original design. We expected our final tube diameter to be 6.35 mm with a mass flow rate of 220 kg/s. y Optimal Tube OD was 8.3mm, adjusted it to 9.525 mm to coincide with standard tube dimensions. The tube length was longer than our original design called for, which was a result of maximizing the q calculated. We set target values for the shell and tube side pressure drops. We set a target range for total weight between 900-1100 kg.
y y
with helical baffles and optimized tube length of 2.6 m. y The ratio between desired and calculated heat rate is 1.00.
Further Analysis
y We believe that cost could be decreased by over-designing
the HE and reducing the number of tubes until we got the desired heat ratio. y The tube mass flow rate was an important design consideration because the outlet temperature of the shell fluid was completely dependent on it. y After performing a macroscopic heat balance, counter flow was chosen because the cold fluid outlet temp was expected to be higher than the hot fluid outlet temp.
designs.
y If multiple tube passes are used with parallel flow it is possible
Cost Summary
y Heat Exchanger Dry Weight
y 730 Kg
y Cost
y OnlineMetals.com y $37.00 per 8ft length of aluminum tubing y Total estimated aluminum tubing cost $337,000.00 y $11.00 per 8ft length of mild steel tubing y Total estimated mild steel tubing cost $100,000.00 y Instillation and Manufacturing