Contents
I. General 2. Definitions 3. Circuit-breaker characteristics 4. Constructional requirements 5. Specific points (appendices) 6. Tests 7. Conclusion 3 8 10 14 21 27 34
DBTP83-En-06/00
General
Standard IEC 60947-2 Came into force in 1999 Takes into account the circuit-breaker main technological upgrades Standard IEC 60947-2 Is internationally recognized and approved
E55225
CSA UL IEC
IEC
JIS/IEC
IEC IEC
IEC IEC
DBTP83-En-06/00
General
constitution
Standard IEC 60947-2 is part of a set of 7 standards characterizing low voltage switchgear
IEC 60 947-2
E55231
or
IEC 60947-1
IEC 60 947-3
or
IEC 60 947-4-1
or
IEC 60 947-4-2
or
Switches
General rules
IEC 60 947-6-2
or
IEC 60 947-7-1
or
...
Terminal block
DBTP83-En-06/00
General
The scope
Standard IEC 60947-2 applies to circuit-breakers, the main contacts of which are intended to be connected to circuits, the rated voltage of which does not in exceed 1000 V AC or 1500 DC;
E58880
041624
DBTP83-En-06/00
031107a
General
The scope
Standard IEC 60947-2 contains additional specifications for: Circuit-breakers suitable for isolation Residual current devices (appendix B) Circuit-breakers with electronic protection (appendices J and F) Circuit-breakers for IT systems (appendix H)
E55226
DBTP83-En-06/00
E55233
General
Standard IEC 60947-2 defines The circuit-breaker classification according to utilization category A or B according to design type air circuit-breaker, moulded case circuit-breaker The circuit-breaker mechanical and electrical data: size, trip unit, etc.
E55235
E55234
DBTP83-En-06/00
E55232
Definitions
Circuit-breaker classification
Utilization category A Circuit-breaker not specifically intended for discrimination Without an intentional short-time delay Without short time withstand current
E55234 E55235
Utilization category B Circuit-breaker specifically intended for discrimination: With intentional short-time delay (adjustable) With short time withstand current
DBTP83-En-06/00
Definitions
Terminology / Vocabulary
Extract from appendix K of standard IEC 60947-2
Characteristics voltage current Ue Ui Uimp In Ith Ithe Icm Icu Ics Icw Ir 1.05 x Ir 1.30 x Ir Isd Ii Rated operational voltage Rated insulation voltage Rated impulse withstand voltage Rated current Conventional free-air thermal current Conventional enclosed thermal current Rated short-circuit making capacity Rated ultimate short-circuit breaking capacity Rated service short-circuit breaking capacity Rated short-time withstand current Adjustable overload setting current Conventional non-tripping current Conventional tripping current Short time delay tripping setting current Instantaneous tripping setting current
short-circuit
trip unit
DBTP83-En-06/00
Circuit-breaker characteristics
Overload withstand
In (in A rms) = rated current Maximum uninterrupted current withstood at ambient temperature, given without abnormal temperature rise Ir (in A rms) = adjustable overload setting current Ir depends on In Ir characterizes the overload protection
E55236
DBTP83-En-06/00
1 0
Circuit-breaker characteristics
Short-circuit withstand
Icu (kA rms) = rated ultimate short-circuit breaking capacity This performance expresses the maximum value of the short-circuit current that can be broken by the circuit-breaker
E55237
DBTP83-En-06/00
1 1
Circuit-breaker characteristics
Short-circuit withstand
Standard IEC 60947-2 introduces a new important performance Ics (as a % of Icu) = rated service short-circuit breaking capacity This performance expresses the suitability of a circuit-breaker to ensure fully normal service after breaking this current 3 times Normal ratio between Ics and Icu
Utilization category A % of Icu 25 50 75 100 Utilization category B % of Icu 50 75 100
E55238
DBTP83-En-06/00
1 2
Safety in use: breaking capacity tests simulate those encountered in "real life"
Prospective short circuit current (Isc) & ultimate short circuit breaking capacity (Icu) when designing an installation, the worst case of short circuit current is calculated : we call this the "prospective short circuit current". prospective Isc: theoretical three phase short circuit at the terminals of the circuit breaker "bolted" short circuit (without arc and impedance) the circuit breaker must be capable of interrupting this short circuit (a fault very unlikely to occur except during commissioning). ultimate short circuit breaking capacity (Icu): maximum short circuit current that the breaker can interrupt. is the only short circuit breaking capacity that needs to be considered when selecting a breaker.
DBTP83-En-06/00
1 3
Safety in use: breaking capacity tests simulate those encountered in "real life"
prospective short circuit level (Isc) & service breaking capacity (Ics) in practice, short circuit currents are much lower than the calculated prospective short circuit level because they are strongly limited by : the impedance of cables and connections the electric arc (within the breaker) its type : phase-neutral or between two phase. reduced short circuits are more probable as they are generally some distance away from the transformer.
DBTP83-En-06/00
1 4
Circuit-breaker characteristics
Short-circuit withstand
Standard IEC 60947-2 introduces a new performance for category B circuit-breakers Icw (in kA rms) = rated short-time withstand current Icw is the maximum short-circuit current that a circuit-breaker can withstand for a short duration (t without deterioration of these characteristics ICW must be at least equal to 12 In or 5 kA for In e 2500 A 30 kA for In > 2500 A The standardized delay time (t is: 0.05 - 0.1 - 0.25 - 0.5 or 1s
E55239
DBTP83-En-06/00
1 5
Constructional requirements
Isolation co-ordination
The circuit-breaker, as a safety device, must be able to withstand Network overvoltages this suitability is characterized by the withstand to the conventional dielectric test at 2 Ui + 1000 - 1 min at power frequency Impulse voltages ( lightning stroke simulation) this suitability is characterized by the withstand to the 1.2/ 50 Qs impulse voltage test of value Uimp
E55242
E55241
DBTP83-En-06/00
E55240
1 6
Constructional requirements
Isolation co-ordination
Uimp (kV peak) = rated impulse withstand voltage Characterization of Uimp Depends on the LV network voltage Depends on the position of the circuit-breaker in the LV network Depends on altitude: Uimp must be valid up to 2000 m tests carried out at +23 % of value
DBTP83-En-06/00
1 7
Constructional requirements
Isolation co-ordination
Characterization of Uimp
Nominal installation voltage Applications
E55243
DBTP83-En-06/00
1 8
Constructional requirements
Isolation co-ordination
Industrial circuit-breaker Uimp = 8 kV Tests to be considered Uimp + 23 % = 9.8 kV standard industrial circuit-breakers and those suitable for isolation
Application of impulse voltage Phase-to-phase Up-to-downstream contacts open Phase-to-earth Impulse voltage value Breakers Disconnector Breakers 9.8 kV 9.8 kV 12.3 kV (*) 9.8 kV 9.8 kV
E55244
(*) 14.7 kV for front face class II circuit-breaker as per IEC 61 140
DBTP83-En-06/00
1 9
Constructional requirements
Circuit-breaker suitable for isolation
Test of isolation suitability 3 tests designed to ensure users that a device suitable for isolation is not dangerous in open position... - even after having eliminated a short-circuit up to Icu - even in the event of overvoltage on the network ... or in closed position cannot be declared open and/or padlockable
DBTP83-En-06/00
2 0
Constructional requirements
Circuit-breaker suitable for isolation
Leakage current measurement test at 110 % of maximum utilization voltage Ue New device, leakage current < 0.5 mA per pole, After breaking at Ics, leakage current < 2 mA per pole, After durability tests, leakage current < 2 mA per pole, After breaking at Icu, leakage current < 6 mA per pole Impulse voltage withstand Uimp = 12 kV (instead of 9.8 kV) between the inlet and the outlet of the open device
(*) 14.7 kV for front face class II circuit-breaker as per IEC 61 140
E55227
Circuit-breaker with a pole held in closed position must not be indicated open and/or lockable by padlock. Padlockable in open position
DBTP83-En-06/00
2 1
Constructional requirements
Circuit-breaker/isolator
Marking A circuit-breaker that is suitable for isolation will display the circuitbreaker/isolator symbol on its front face
E55246
DBTP83-En-06/00
2 2
DBTP83-En-06/00
2 3
E55253 DBTP83-En-06/00
2 4
E55250
I fault
Class A cycle
DBTP83-En-06/00
2 5
E55254
Hygro (%)
100 90
0 t (C) 55
12 14h30
duration (h)
25
DBTP83-En-06/00
2 6
DBTP83-En-06/00
2 7
PIM
DBTP83-En-06/00
2 8
Tests
Standard IEC 60947-2 makes provision for complete device testing Cumulative tests grouped into sequences One sample undergoes all the sequence tests 5 Test Sequences + 1 Combined test sequence All the functions and characteristics are tested Specific tests Circuit-breaker suitable for isolation Residual current device, Circuit-breaker with electronic trip unit, EMC Tests etc.
DBTP83-En-06/00
2 9
Tests
Test sequences
Category A Sequence 1 General operating characteristics Sequence 2 Service breaking capacity Ics Sequence 3 Ultimate breaking capacity Icu Sequence 4 Rated short time withstand current Icw Combined test sequence Example Category B Ics < Icu Icw = Ics = Icu
Masterpact N1-H1
DBTP83-En-06/00
3 0
Test sequences
Example Sequence 1 and 2
Test sequences Circuit-breaker type Cat. A Cat. B Icw Icw < Ics = Ics Tests to be performed in turn on the same circuit-breaker Icw = Ics = Icu 1. Verification of tripping thresholds 2. Dielectric properties 2.1 If an Uimp is declared by the Manufacturer: Uimp Test phase-to phase, phase-to-earth 2.2 If no Uimp is declared Dielectric test 50 Hz at 2Ui + 1000 3. Mechanical durability 4. Electrical durability 5. Operation in overload at 6 In 6. Dielectric withstand at 2 Ue (min. 1000 V) 7. Temperature rise at In 8. Verification of non-drift of overload trip units 1. Three successive current breakings Ics as per cycle O - 3 mm - CO - 3 mm - CO 2. Verification of suitability for operation, achievement of 5 % of electrical durability 3. Dielectric withstand at 2 Ue (50 Hz-1 mm) 4. Temperature rise at In 5. Verification of non-drift of overload trip units Additional tests for circuit-breakers declared suitable for isolation 1. Ditto 2. Dielectric properties Uimp withstand compulsory: ditto opposite plus between Inlet and Outlet: Uimp + 25 % and leakage current test
(< 0.5 mA per pole at 110 % Ue)
E55255
4. Ditto 5. Ditto
DBTP83-En-06/00
3 1
Tests
Tripping curves all the important points on the tripping curve are tested essential features are tested in real and the hardest conditions
E55228
DBTP83-En-06/00
3 2
Tests Icu
In sequence 3 of standardized tests O - t - CO test Verifications Dielectric at 2 Ui (minimum 1000 V) for 1 minute,
NB: for circuit-breaker suitable for isolation test of leakage I = < 6 mA at 110 % Ue
Standard IEC 60947-2 clarifies the definition of circuit-breaker breaking capacity The circuit-breaker must not be dangerous after 2 breakings at Icu
DBTP83-En-06/00
3 3
Tests Ics
In sequence 2 of standardized tests O - t - CO - t - CO test Verifications Dielectric at 2 Ui (minimum 1000 V) for 1 minute, NB: for circuit-breaker suitable for isolation test of leakage I e 2 mA at 110 % Ue Of suitability to break its nominal current by achieving 5% of electrical durability Of temperature rise at In, Verification of overload trip units at Ir The circuit-breaker must be suitable for operation after a short circuit at Ics. This performance is guaranteed 3 times. The Ics performance represents a practical breaking capacity.
DBTP83-En-06/00
3 4
Tests Icw
In sequence 4 of standardized tests Category B circuit-breaker Verifications Device withstand at Icw and (t indicated by the manufacturer Of temperature rise at In, after O - t - CO cycle at Icw at maximum voltage Dielectric at 2 U 1(minimum 1000 V) for 1 minute, Overload trip units at 2 Ir
DBTP83-En-06/00
3 5
Conclusion
Standard IEC 60947-2
E55230
CT150fi DBTP83-En-06/00
3 6
Conclusion
Standard IEC 60947-2
E55258 E55234
28 kA
8.5 kA
probable Isc very close to prospective Isc: Ics = 100 % Icu NS160N is optimized
probable Isc less than prospective Isc: Ics = 50 % Icu C60L is optimized
DBTP83-En-06/00
3 7
E55259 E55260
160 A
Conclusion
E55256
CT150fi
E55230
A circuit-breaker certified according to Standard IEC 60947-2 guarantees a quality device with durable performance of all its safety functions.
DBTP83-En-06/00
3 8