SUBSTATION
GEN
MSB
Tx
RMU
RMU
C.BREAKER
RMU 11KV
Rating Rated voltage Withstand voltage 1 minute Impulse withstand voltage Frequency Load Break Switch Rated current disconnector Fuse switch Rated current Fuse rating Unit kV kV rms kV Hz nos A nos A A 500 kVA 12 28 75 50 2 630 1 200 63 1000 kVA 12 28 75 50 2 630 1 200 80
VOLTAGE RATING
12 kV 17.5kV 24kV
CURRENT RATINGS
400A 630A
DISTRIBUTION TRANSFORMER
Rating Voltage ratio at no load Off circuit tapping Withstand voltage 1 minute Impulse withstand voltage Frequency Vector group Type of cooling Unit 500kVA V 11/.433 % 2.5, 5 kV 28 kV 75 Hz 50 Dyn11 ONAN 1000kVA 11/.433 2.5, 5 28 75 50 Dyn11 ONAN
L.V BOARD
Rating Rated current Rated voltage Incoming disconnector Outgoing Fuseway at 20 C Outgoing fuse rating C.T ratio (class 0.2) MD meter P.F meter kWh meter Unit 500kVA 1000kVA A 800 1600 V 1000 1000 A 800 1600 A 400 400 A 160 160 800/5A 1600/5A nos 3 3 nos 1 1 nos 1 1
ENCLOSURE
Internal Arc testing IEC 1330 18.4 kA 1 sec Clause 6 Temperature rise test IEC Class 10 enclosure 1330 Clause 4.1 Index Protection (IP) IP 35 Sound Level test Material/Thickness Base Frame 60 dBA Electro Galvanised sheet/3.0mm Hot dipped Galvanised CChannel
VOLTAGE INDICATOR