Fire fighting Installation system

Bill of Quantities

ITEM

DESCRIPTION

UNI T

QTY

RAT E

RM

CEN T

FIRE FIGHTING INSTALLATION, TESTING, COMMISSIONING AND MAINTENANCE OF FIRE FIGHTING SYSTEM. HOSE REEL SYSTEM No. Swing hose-reel complete with 25mm diameter x 30mm long hose,12.5mm diameter nozzles, fixing, bracket, reducer, gate valve and other accessories as described. No. Hot-dipped galvanized pressed steel water storage tank of approved type, manufactured to BS 1564, 3.66m x 2.44m x 1.22m height with 2400 gallons capacity, complete with float valve, level indicator, ladder, overflow pipe and drain pipe, at approximately 1000mm high above ground level. Electrical duty pump, 30 igpm, 150 ft. head. Diesel standby pump, 32 igpm, 160 ft. head. TESTING Allow for testing the foregoing fire fighting system, make good any defects and leave the whole of the installation in perfect working order to the satisfaction of the S.O and Local Authority. Item 1 20

No. No.

1 1

Preambles

The drawing where the drawing no. FNP/BL/0205/F01-04 shows the layout of the fire fighting system.All quantities are all provisional subject to remeasurement upon combination construction of the said item. The fire fighting system to be excuted by the contractor in accordance to Jabatan Bomba Malaysia requirement and approval. All wiring to brickwall and soffit of ceiling shall be concealed unless otherwise stated and all wiring above ceiling space of roof level shall be in galvanised iron conduit and coloured by red. The item of this bill not fully described and the rates shall be held to include for all short running, bend,tees,joints,valve,reducer,backnuts and the like.The contractor must allow for testing fire fighting system and handling over the test certificate to the architect. The contractor shall be provide for obtaining all necessary plan.

ITEM

DESCRIPTION

UNIT

QTY

RATE

RM

CENT

FIRE FIGHTING INSTALLATION, TESTING, COMMISSIONING AND MAINTENANCE OF FIRE FIGHTING SYSTEM. HOSE REEL SYSTEM Swing hose-reel complete with 25mm diameter x 30mm long hose,12.5mm diameter nozzles, fixing, bracket, reducer, gate valve and other accessories as described. Hot-dipped galvanized pressed steel water storage tank of approved type, manufactured to BS 1564, 3.66m x 2.44m x 1.22m height with 2400 gallons capacity, complete with float valve, level indicator, ladder, overflow pipe and drain pipe, at approximately 1000mm high above ground level. Electrical duty pump, 30 igpm, 150 ft. head. Diesel standby pump, 32 igpm, 160 ft. head. TESTING Allow for testing the foregoing fire fighting system, make good any defects and leave the whole of the installation in perfect working order to the satisfaction of the S.O and Local Authority. No. 20

No.

No. No.

1 1

Item

Description ELEMENT FIRE FIGHTING INSTALLATION Fire-Fighting in connecting (internally) Fire Alarm system Manual Break glass fire alarm with 24 volts D.C supply, mounted at wall as described 150 mm Diameter fire alarm bell with 24 volts D.C supply, mounted as described Fire Fighting Equipment Lighting Installation (internally) KELUAR' Sign complete with nickel Cadmium batteries, tuber, etc and accessories with approved 13 W non-contained fluorescent Self contained Emergency Light fitting complete with nickel cadmium battery and outomatic charger unit similar econ lite Hose Reel system

QTY

Unit

Rate

APARTMENT J.B RM SEN

NO

NO

NO

NO

Hot Dipped Galvanised Pessed Steel Water Storage Tank of approved type, manufactured to BS 1564, 3m x 2m x 2m height with 2640 Gallons capacity, complete with 50 diameter overflow pipe,suction pipe, drain pipe incoming pipe at approximately 100 mm above ground level 1" Diameter Swing Type Hydraulic hose reel drums each c/w diameter x 100 ft. non. Kink double braided tubing and 1" diameter 3 jet spray nozzle Electrical Duty Pump, 30 IGPM, 120 ft head Diesel Standby Pump, ditto Galvanised Iron class 'B' Tubing to comply with BS 1387, screw socket together

NO

NO

G H

1 1

NO NO

50 mm Diameter incoming pipe, at High level free standing 50 mm Diameter overflow pipe,ditto

2.00

Description Galvanised Iron class 'B' Tubing to comply with BS 1387, screw socket together 50 mm Diameter suction pipe at low level, free standing 25 mm Diameter riser pipe fixed to brickwall 50 mm Diameter drain pipe at low level and jointing to Galvanised iron pipe

QTY

Unit

Rate

APARTMENT J.B RM SEN

B C

3 2

M M

Brasswork To Comply With BS 1010 as described :50 mm Diameter flexible connection and 2 jointing to galvanised iron pipe 50 mm Diameter Check valve, ditto 50 mm Diameter stop valve, ditto 50mm Diameter Ball float valve, ditto 50mm Diameter gate valve, ditto 50mm Diameter outomatic air release valve, ditto 50mm Diameter pressure gauge, ditto 50mm Diameter stairer valve, ditto BUILDER'S WORK 2 2 2 2 2

NO

E F G H J

NO NO NO NO NO

K L

1 2

NO NO

Wire brush and painting primer, undercoat and two coat gloss oil to surface of galvanised iron pipe Installation inclusive of hacking, punching of holes in wall and floors, coring of holes through reinforce concrete slab and making good Testing

Item

Item

Allow for testing foregoing fire fighting system, make good and any defects and leave the whole of the installation in perfect working order to the satisfaction of the S.O and Local Authority

Item

PROJEK
Cadangan Merekabentuk, Membina & Menyiapkan SMK Kenangan, Segamat, Johor, Di atas Lot 5848, 2259 Sebahagian Lot 5848 dan Sebahagian Lot 2258.

ABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN. DESCRIPTION ELEMENT : FIRE FIGHTING INSTALLATION (INTERNALLY) PREAMBLE ( All Provisional ) The fire fighting installation is to be executed by contrator in accordance with Jabatan Bomba requirement and approval. Where items in this bill are not fully describes the rates shall be held to include for all piping, control gear and etc all as described or as required by Jabatan Bomba as being appropriate for installation. The rates be held to include for all short running lengths, bends, tees and etc. The contractor must allow for testing the fire fighting installation and handling over the test certifiate to the Architect. (Q.1) HOSE-REEL SYSTEM Hydraulic hose-reel complete with 36 mm x 25 mm diameter long hose, 12.5 mm diameter nozzles, fixing, bracket, reducer, gate valve and other accessories as described. (Q.19) Electrical duty pump with 30 IGPM at 135 feet head. (Q.19) UNIT QTY RATE RM

Item

No No No

1 1 1

Diesel standby pump with 130 IGPM at 135 feet head. (Q.19) Galvanised Iron Class 'B' Tubing to Comply With BS 1387 Screw Socketed Together Including All Necessary Short Length, Fire Bends, Tees, Dimishing Pieces, Plugs and The Like as Described. 50 mm Diameter incoming pipe laid in trench. (Q.8)

13

50 mm Diameter distribution pipe laid in ground slab.

(Q.8)

17

50 mm Diameter distribution pipe fixed in ceiling space horizontally with approved brackets. (Q.8) 50 mm Diameter distribution pipe fixed to brickwall vertically with approved brackets. (Q.8) 25 mm Diameter distribution pipe fixed to hidraulic hose-reel. (Q.8) EXTRA OVER 50 mm Diameter elbow. (Q.8.1)

23

17

M No

1 11

TO COLLECTION FF / 01

PEJABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN. ITEM DESCRIPTION ELEMENT : FIRE FIGHTING INSTALLATION (INTERNALLY) A B C EXTRA OVER 50 mm Diameter tee. EXTRA OVER 25 mm Diameter elbow. (Q.8.1) (Q.8.1) No No 1 2 UNIT QTY

(CONT'D) RATE RM

12 mm Diameter mild steel brackets at 600 mm centres to centres to support galvanised iron pipe. (Q.12.4) Brasswork to Comply with BS 1010 as Described.

No

68

50 mm diameter gate valve and jointing to galvanised iron pipe. (Q.19) Hot-dipped galvanised pressed steel water storage tank opproved type, manufactured to BS 1564, 12' x 4' x 8' height with 1000 gallons capacity, complete with float valve, level indicator, ladder, overflow pipe and drain pipe at ground level. (Q.19) Sundries Testing and commissioning the hose-reel system as described in the specification. (Q.30.4) PORTABLE FIRE EXTINGUISHER

No

No

Item

9 kg ABC extinguisher dry powder bomba approved type manufactured to BS 5306, complete with brackets and accessories. (Q.19) Sundries

No

Testing and commissioning the portable fire extinguisher as described in the specification. (Q.30.4) FIRE ALARM SYSTEM

Item

150 mm Diameter fire alarm bell with 24 V (D.C) supply mounted at wall as described. (Q.19) Manual break glass fire alarm size 84 mm x 115 mm with 24 V (D.C) supply mounted at wall as described. (Q.19) PVC Insulated Cable Drawn into Concealed Galvanised Iron Conduit. (measured separately)

No

No

2 x 2.5 mm2 cable. TO COLLECTION FF / 02

(Q.19.4)

54

PEJABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN. ITEM DESCRIPTION ELEMENT : FIRE FIGHTING INSTALLATION (INTERNALLY) Galvanised Iron Class 'B' Conduit with Screw Joints Including All Short Running Length, Bends, Tees, Saddles Crampets, Locknuts, Circular Boxes as Described. A 50 mm Diameter conduit, chase into brickwall vertically with approved bracket. (Q.19.4) 50 mm Diameter conduit, fixed in ceiling space with approved bracket. (Q.19.4) Sundries C Testing and commissioning the fire alarm system as described in the specification. (Q.30.4) BUILDER'S WORK D Excavate trench to receive 50 mm diameter incoming pipe, maximum depth nearest to 0.25 m including filling in, compaction and disposal of surplus soil as desribed. (Q.32.1) 600 mm thick vibrated reinforced conrete grade 20 as concrete plinth including all necessary formwork and reinforcement. (F.3.19) Allow for testing the foregoing fire fighting installation, make good any defect and leave the whole of the installation in perfect working order to the satisfaction of the S.O and Local Authority. (Q.30.4) UNIT QTY

(CONT'D) RATE RM

17

37

Item

18

m2

Item

TO SUMMARY FF / 03

Taking Off list


Builders Work Excavate trench to receive pipe - M Hose Reel System Swing hose reel - NO Water storage tank - NO Electrical duty pump - NO Diesel standby pump - NO Piping 50 mm Diameter incoming pipe - M 50 mm Diameter rising pipe M 50 mm Diameter distribution pipe - M Brasswork 50 mm Diameter air release valve NO 50 mm Diameter gate valve NO 50 mm Diameter check valve NO 50 mm Diameter strainer valve NO 50 mm Diameter flexible joint NO 25 mm Diameter gate valve NO

Cable

2 x 1.5 mm2 cable 2.5 mm2 cable Fire Alarm System Control gear NO Junction box NO Manual break glass NO 2 x 2.5 mm cable M 50 mm Diameter conduit M Portable Fire Extinguisher 9 kg Fire extinguisher - NO Hydrant Hose Cabinet NO Lighting Installation Keluar sign - NO 5A Emergency light NO Testing Allow for testing the foregoing fire fighting system ITEM

Taking Off List

1. 2. 3. 4. 5. 6. 7. 8. 9. 10.

Pumps. Pipeworks. Tee Bend. Valves and ancillaries. Hydrant box. Pillar. Fire Extinguisher. Electrical Works. Testing.

- No -M - No - No - No - No - No - No - No - Item

1. Pumps - No

Equipment - Pumps

Electric Fire pump, end suction centrifugal type with capacity of 750 GPM, 7 bar, 81 Kw/ N 108.7 Bhp. o 1

(PU 1 20 2)

2. Pipeworks

150mm dia. Black steel pipe, ERW. Sch 40, 130 embedded in in situ concrete . 0 0

130 . 0 0 Leng (Pump Room) t h 75,0 0 0 55,0 0 0

130,
0 0 0

3. Fitting and Accessories

Tees

EXTRA OVER 150x150x65mm Black steel tee.

N o 5

L.Basem en t

Bend

EXTRA OVER Bend 90, to 150mm dia Black steel pipe

N o 1

L.Baseme nt

4.Hydrant

Hydrant

Indoor hydrant box size 800x1300x300mm, complete with house rack, hydrant valve and fire N house type 40x25m. o 12

3 3 3

L.Base m en t

L. Dasar

3
3 3 3 3 L. 2 L. 1

12

5. Fire Extinguisher

Fire extinguisher capacity 3 Kg complete with box, and all necessary supporting fixing N accessories as specified. o . 52

L.B L . 2 52

13

6. Testing

Allow for checking, testing, acceptance testing and commisioning the Fire Protection Installation. It e m

7. Maintenance

Allow for service and maintenance of the complete installations during 12 months Defects Liability Period, excluding any maintenance resulting from defective workmanship or materials requiring repair

and/or replacement by contractor.

It e m

Item

Description Element Fire Fighting Installation Builder's Work

Unit

Rate

Qtty

RM

Excavate trench to receive 150mm diameter incoming pipe, maximum depth not exceeding 1.0m including filling in, compaction and disposal of surplus soil as required.

17

Excavate trench to receive 50mm diameter Galvanised Iron class 'B' incoming pipe, maximum depth not exceeding 1.0m including filling in, compaction and disposal of surplus soil as described. Hose Reel System

Swing type hose reel drum with corrugated hose 30.5x25mm diameter complete with valve, bracket, 12.5mm diameter nozzle and other accessories as described.

no

Hose reel cabinet type SRI model HRS 045 or equivalent for all hose reel drum

no

Electrical duty pump with the capacity of 30 igm againts 170 ft static head complete with wiring, pump plinth and other accessories

no

Diesel standy pump with the capacity of 30 igm againts 170 ft static head complete with wiring, pump plinth and other accessories. One (1) nos of 2400 gallons of hose reel water tank, 6mm thick press steel panel complete with ball valve, fittings, level indicator, float control, piping, external red paint, internal asnd external ladder and other accessories.

no

no

To collection

Item

Description Galvanised Iron Class 'B' Tubing Screw Socketed Together Including All Necessary Short Length, Sockets, Connectors, Backnuts, Elbows And The Likes As Described

Unit

Rate

Qtty

Rm

A 150mm Diameter incoming pipe laid in trench m (m/s) B 50mm Diameter incoming pipe embedded m into ground floor slab C 50mm Diameter incoming pipe fixed to m brickwall Brasswork To Comply To BS 1010 As Described A 50mm Diameter air release valve and jointing no to galvanised iron pipe B 50mm Diameter check valve and jointing to no galvanised iron pipe C 65mm Diameter gate valve and jointing to no galvanised iron pipe

17

To collection

Item

Description Fire Alarm System Installation

Unit

Rate

Qtty

Rm

A Main fire alarm console panel (6 zones) no complete with LED mimic diagram, battery compartment complete with 8 AHx24V and charger as manufacturer's detail. B 400x400x150mm fixed to wall junction box no approved type and quality, complete with 3mm thick galvanised steel covers, gasket and all other necessary accessories. C Manual break glass fire alarm size no 84mmx115mm with 24v(d.c) supply mounted at wall as described D 150mm Diameter fire alarm bell with 24v (d.c) suplly mounted at wall as described Testing A Allow for testing the foregoing fire fighting Item system, make good any defect and leave the whole installation in perfect working order to the satisfaction of the superitandant officer. no

To collection

THANK YOU