Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 27

Biosco: MV/LV prefabricated

substations IEC 62271-202 Presentation of the standard

Safety is a choice

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

> Introduction

Standard IEC 62271-202: an international influence

Biosco conforms to IEC 62271-202 international standard

IEC 62271-202 standard applies to most of prefabricated substations world-wide.

UL

IEC IEC IEC

IEC

IEC

Biosco - Prsentation clientle - 08/2007

> Introduction

Introduction

IEC 62271-202 standard specifies the rated characteristics, the design and construction rules and the test methods applicable to prefabricated substations.

A prefabricated substation is defined as a type-tested assembly comprising an enclosure that includes:


Transformer LV switchboard MV switchboard MV and LV interconnections Auxiliary equipment

Biosco - Prsentation clientle - 08/2007

> Introduction

Introduction

These substations are located in places accessible to the general public. Consequently, safety of persons must be guaranteed Conformity to the IEC standard guarantees: Protection of the general public Protection of operators

Biosco - Prsentation clientle - 08/2007

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

> Type-tested substations

Type-tested equipment
All substation components must conform to IEC standards and in particular:

Transformers: IEC 60076-1 or 60076-11

MV switchboard: IEC 62271-200 or 62271-201

LV switchboard: IEC 60439-1 and IEC 60947-1

Biosco - Prsentation clientle - 08/2007

> Type-tested substations

The prefabricated substation undergoes type tests

Use of equipment conform to IEC standards


Functional tests Electromagnetic compatibility Temperature class Non flammable materials Earthing circuit test LV

Mechanical resistance of the enclosure Sound level Degree of protection Insulation level

MV

Internal arcing withstand


Oil retention

Biosco - Prsentation clientle - 08/2007

> Type-tested substations

The 4 designs of the Biosco range conform to IEC 62271-202 standard


Biosco W: Substation with corridor Operation protected from bad weather conditions Biosco N: Substation with external operation Ground space savings Biosco H: Half-buried substation Visual impact limited Biosco U: Underground substation Blends completely into the environment

Biosco W

Biosco N

Biosco H

Biosco U

Biosco - Prsentation clientle - 08/2007

10

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

11

> The type tests

The type tests

1. Dielectric tests 2. Temperature rise tests 3. Main circuit and earthing tests 4. Functional tests 5. Degree of protection verification tests 6. Mechanical tests 7. Arcing due to an internal fault tests

8. Sound verification tests


9. Electromagnetic compatibility tests

Biosco - Prsentation clientle - 08/2007

12

> The type tests

Dielectric tests
Aim of test To guarantee insulation of HV and LV interconnections

Our performance The HV and LV interconnections of the Biosco range are tested as per standards IEC 60694 and 60439 Example for 24 kV switchgear: Withstand to voltage of 50 kV at power frequency for 1 min Withstand to lightning impact voltage tests for a 1.2 s wave and a voltage of 125 kV

Biosco - Prsentation clientle - 08/2007

13

> The type tests

Temperature rise tests


Aim of test

To determine the enclosure class To guarantee that none of the substation components will overshoot its standard-defined limits To guarantee temperature on the parts of the enclosure likely to be touched during operation To guarantee lifetime of insulating devices and thus safety of equipment during the period of operation

Our performance

The Biosco substation enclosures are class 10 as standard This performance can be adapted to your needs according to ambient temperatures, degrees of protection or transformer losses Numerical modelling and thermal simulations are performed.
14

Biosco - Prsentation clientle - 08/2007

> The type tests

Main circuit and earthing tests


Aim of test:

To guarantee the capacity to withstand short-circuit currents

Our performance

The Biosco substations are tested up to 12 kA

Biosco - Prsentation clientle - 08/2007

15

> The type tests

Functional tests
Aim of tests To guarantee that it is possible to carry out all the operations required for commissioning, operation and maintenance Our performance The Biosco substations undergo a series of verifications Switchgear operation Mechanical operation of substation doors Reading transformer temperatures and oil levels Monitoring voltage readings Installation of earthing devices Cable tests Replacement of fuses and monitoring of locking systems Operating the transformer on-load tap changer Cleaning the ventilation grids Monitoring the locking systems

Biosco - Prsentation clientle - 08/2007

16

> The type tests

Degree of protection verification test


Aim of test To ensure the protection of people against access to hazardous parts To guarantee the protection of equipment against ingress of foreign solid objects and water.

Our performance The degree of protection of the Biosco substations is between IP23 and IP54 This performance can be adapted to your needs: stipulations of standards and climatic requirements.

Biosco - Prsentation clientle - 08/2007

17

> The type tests

Mechanical tests
Aim of test To guarantee withstand of roof in event of overload: people, snow, etc. To guarantee the resistance of substation to wind pressure and to mechanical impacts on walls, covers, doors, ventilation opening.

Our performance

Roof withstand greater than 250 daN/m IK10 (including doors and ventilation grids)

Biosco - Prsentation clientle - 08/2007

18

> The type tests

Arc due to an internal fault test


Aim of test To guarantee the protection of operators and the general public. The standard defines a classification: Class A: operator protection Class B: general public protection Class AB: operator and general public protection Our performance Koolarc system (cools and reduces pressure of arc gases) Classification for all substation types Example Biosco N India IAC-AB-20kA-1s

Pressure and temperature simulation

Biosco - Prsentation clientle - 08/2007

19

> The type tests

Sound verification test

Aim of test

To ensure that the substation enclosure does not increase the transformer noise level.

Our performance

The Biosco substations conform to the requirements of the IEC standard

Biosco - Prsentation clientle - 08/2007

20

> The type tests

Electromagnetic compatibility test


Aim of test

To satisfy emission requirements laid down by international standards To guarantee the proper operation of equipment in an environment comprising large electromagnetic disturbance sources

Our performance

HV and LV switchgear comply with the specifications of standards IEC 60694 and 60439-1. Electromagnetic fields are simulated.

Biosco - Prsentation clientle - 08/2007

21

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

22

> A specification tool

A specification tool
Standard IEC 62271-202 tells users which information should be supplied for invitations to tender and orders.

Network specificities Nominal and highest voltages Frequencies Neutral earthing mode Operating conditions Minimum and maximum temperatures Altitudes
The specificities and electrical characteristics of prefabricated substations Voltage, power, frequency

Biosco - Prsentation clientle - 08/2007

23

> A specification tool

A specification tool
The information required for specifications is summarised in table form. All the electrical utility has to do is complete this information.

Biosco - Prsentation clientle - 08/2007

24

Contents
Introduction Type-tested substations The type tests A specification tool Conclusion

Biosco - Prsentation clientle - 08/2007

25

Conclusion
Type-tested MV, LV equipment and transformer

A series of type tests to guarantee safety and reliability of the prefabricated substation throughout its life cycle.

Use of equipment conform to IEC standards Electromagnetic compatibility Functional tests Temperature class Non LV flammable materials Earthing circuit test

Mechanical resistance of the enclosure Sound level Insulation level MV Internal arcing withstand Oil retention

An MV/LV substation specification guide providing all characteristics and installation and operation conditions

Biosco - Prsentation clientle - 08/2007

26

Thank you for your attention

Biosco - Prsentation clientle - 08/2007

27

You might also like